The stage settings vary depending on which control function they are a part of. By default only one
setting group of the eight available setting groups is activated. You can enable more groups in the
Control
→
Setting groups menu, although they are set here in the "Settings" section.
Figure. 4.5 - 27. Registers section.
Please note that the content of the "Registers" section is not available in the HMI. It can only be
accessed via the AQtivate setting tool. Stored in the "Registers" section you can find both "Operation
event register" and "General event register".
"Operation event register" stores the function's specific operation data. There are twelve (12) registers,
and each of them includes data like the pre-fault value, the fault value, the time stamp and the active
group during the trigger. Data included in the register depend on the control function. You can clear the
the operation register by choosing "Clear registers"
→
"Clear".
"General event register" stores the event generated by the stage. These general event registers cannot
be cleared.
A
AQ
Q-C213
-C213
Instruction manual
Version: 2.04
31
Содержание AQ-C213
Страница 1: ...AQ C213 Capacitor bank protection IED Instruction manual ...
Страница 308: ...Figure 7 4 184 Example block scheme A AQ Q C213 C213 Instruction manual Version 2 04 307 ...
Страница 330: ...Figure 8 14 207 Panel cutout dimensions and device spacing A AQ Q C213 C213 Instruction manual Version 2 04 329 ...