Figure. 7.1 - 177. AQ-C213 application example with function block diagram.
Protection functions
Control functions
Device I/O
AQ-C213
DI
4+2
DO
5+1
CT
3 (IL)
2 (I0)
Add-on
3 slots
Monitoring functions
THD
31st
CTS
DR
Disturbance
recorder
VTS
U>
59
(4)
U<
27
(4)
U0>
59N
(4)
Voltage-based
VT
3 voltage
channels
OBJ
SOTF
Switch-on-
to-fault
SGS
1...8
Current-based
I>
50/51
(4)
I0>
50/51N
(4)
Ih>
(4)
50H/51H
/68H
(4)
U1/U2>/<
47/27P
/59PN
TF>
49F
(1)
CBFP
50/52BF
(1)
Iuc>
46C
(1)
I<
37
(1)
I2>
46/46R
/46L
(4)
OPTIONAL
Iarc>/I0arc>
50Arc/50NArc
7.2 Application example and its connections
This chapter presents an application example for the capacitor bank protection IED.
Since two line-to-line voltages and the zero sequence voltage (U3) are connected, this application
uses the voltage measurement mode "2LL+U0" (see the image below). Additionally, the three-phase
currents are also connected. The digital inputs are connected to indicate the breaker status, while the
digital outputs are used for breaker control.
A
AQ
Q-C213
-C213
Instruction manual
Version: 2.04
301
Содержание AQ-C213
Страница 1: ...AQ C213 Capacitor bank protection IED Instruction manual ...
Страница 308: ...Figure 7 4 184 Example block scheme A AQ Q C213 C213 Instruction manual Version 2 04 307 ...