Settings
Table. 5.2.2 - 25. Settings of the VT scaling.
Name
Range
Step Default
Description
Voltage
measurement
mode
0: 3LN
1: 2LL+U0
(3LN)
2: 2LL+U0
(Open delta
2LL)
3: 2LL+U0
4: 1LL+U0
-
0: 3LN
The relay's voltage wiring method. The voltages are scaled according the
set voltage measurement mode.
Voltage
measurements
0: No PE
voltages
avail.
1: PE
Voltages
calculated
2: PE
Voltages
measured
3: PP
voltages
calculated
4: No full
voltages
available
5: Only U0
available
6: 1Phase-
Phase
measurement
+ U0"
-
-
Indicates whether or not phase-to-earth voltages are available. Also
indicates whether P-E voltages are measured from the voltage channels
directly or if they are calculated from line-to-line and line-to-neutral
voltages.
VT primary
1…1 000
000.0 V
0.1V
20
000.0V
The rated primary voltage of the voltage transformer.
VT secondary
0.2…120.0 V 0.1V
100.0V
The rated secondary voltage of the voltage transformer.
U3 Res/SS VT
primary
1…1 000
000.0 V
0.1V
20
000.0V
The primary nominal voltage of the connected U0 VT. This setting is
visible for all modes except "3LN".
U3 Res/SS VT
secondary
0.2…120 V
0.1V
100.0V
The secondary nominal voltage of the connected U0 VT. This setting is
visible for all modes except "3LN".
U1 Polarity
0: -
1: Invert
-
0: -
The selection of the first voltage measurement channel's (U1) polarity
(direction). The default setting is for the positive voltage to flow from
connector 1 to connector 2, with the secondary voltage's starpoint
pointing towards the line.
U2 Polarity
0: -
1: Invert
-
0: -
The selection of the second voltage measurement channel's (U2) polarity
(direction). The default setting is for the positive voltage to flow from
connector 1 to connector 2, with the secondary voltage's starpoint
pointing towards the line.
U3 Polarity
0:-
1:Invert
-
0:-
The selection of the third voltage measurement channel's (U3) polarity
(direction). The default setting is for the positive voltage to flow from
connector 1 to connector 2, with the secondary voltage's starpoint
pointing towards the line.
VT scaling
factor P/S
-
-
-
A relay feedback value; the calculated scaling factor that is the ratio
between the primary voltage and the secondary voltage.
VT scaling
factor p.u. Pri
-
-
-
A relay feedback value; the scaling factor for the primary voltage's per-
unit value.
VT scaling
factor p.u. Sec -
-
-
A relay feedback value; the scaling factor for the secondary voltage's per-
unit value.
A
AQ
Q-C213
-C213
Instruction manual
Version: 2.04
72