Event number
Event channel
Event block name
Event code
Description
8449
132
VUB3
1
Start OFF
8450
132
VUB3
2
Trip ON
8451
132
VUB3
3
Trip OFF
8452
132
VUB3
4
Block ON
8453
132
VUB3
5
Block OFF
8512
133
VUB4
0
Start ON
8513
133
VUB4
1
Start OFF
8514
133
VUB4
2
Trip ON
8515
133
VUB4
3
Trip OFF
8516
133
VUB4
4
Block ON
8517
133
VUB4
5
Block OFF
The function registers its operation into the last twelve (12) time-stamped registers; this information is
available for all provided instances separately. The register of the function records the ON event
process data for START, TRIP or BLOCKED. The table below presents the structure of the function's
register content.
Table. 5.3.11 - 116. Register content.
Date and time
Event code
Trigger
voltage
Fault
voltage
Pre-fault
voltage
Trip time
remaining
Used SG
dd.mm.yyyy
hh:mm:ss.mss
8320 -
8517 Descr.
Start average
voltage
Trip -20ms
averages
Start -200ms
averages
0 ms...1800s
Setting
group 1...8 active
5.3.12 Non-directional undercurrent protection (I<; 37)
The non-directional undercurrent function is used for instant and time-delayed undercurrent protection.
The operating decisions are based on phase current magnitude, constantly measured by the
function. The available phase current magnitudes are equal to RMS values. The blocking signal and the
setting group selection control the operating characteristics of the function during normal operation,
i.e. the user or user-defined logic can change function parameters while the function is running.
The outputs of the function are the START, TRIP and BLOCKED signals. The undercurrent function
uses a total of eight (8) separate setting groups which can be selected from one common source.
The function can operate on instant or time-delayed mode. In the time-delayed mode the operation can
be set to operate on definite time (DT) delay.
The inputs for the function are the following:
• setting parameters
• digital inputs and logic signals
• measured and pre-processed current magnitudes.
The function outputs the START, TRIP and BLOCKED signals which can be used for direct I/O
controlling and user logic programming. The function generates general time-stamped ON/OFF events
to the common event buffer from each of the three (3) output signals. In the instant operating mode the
function outputs START and TRIP events simultaneously with an equivalent time stamp. The time stamp
resolution is 1 ms. The function also provides a resettable cumulative counter for the START, TRIP and
BLOCKED events.
A
AQ
Q-C213
-C213
Instruction manual
Version: 2.04
169