Reset
Reset ratio
0.020 Hz
Instant reset time and start-up reset:
- I
M
/I
SET
ratio +/- 50 mHz (Fixed)
- I
M
/I
SET
ratio +/- 50 mHz (Tracking)
<110 ms (max. step size: 100 mHz)
<3 cycles or <70 ms (max. step size: 100 mHz)
No
Notte!
e!
• The secondary voltage must exceed 2 volts or the current must exceed 0.25 amperes (peak-
to peak) in order for the function to measure frequency.
• The frequency is measured two seconds after a signal is received.
• The fixed frequency mode: When the fixed mode is used, the system's nominal frequency
should be set to 50 or 60 Hz.
• The tracked frequency mode: When tracked mode is used, the system's nominal frequency
can be anything between 7...75 Hz.
9.2.1.11 Line thermal overload protection (TF>; 49F)
Table. 9.2.1.11 - 253. Technical data for the line thermal overload protection function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input magnitudes
TRMS phase currents (up to the 31
st
harmonic)
Settings
Time constants τ
1
Time constant value
0.0…500.00 min, step 0.1 min
Service factor (maximum overloading)
0.01…5.00 × I
N
, step 0.01 × I
N
Thermal model biasing
- Ambient temperature (Set –60.0…500.0 deg, step 0.1 deg and RTD)
- Negative sequence current
Thermal replica temperature estimates
Selectable between °C and °F
Outputs
- Alarm 1
- Alarm 2
- Thermal trip
- Trip delay
- Restart inhibit
0…150 %, step 1 %
0…150 %, step 1 %
0…150 %, step 1 %
0.000…3600.000 s, step 0.005 s
0…150 %, step 1 %
Inaccuracy
- Starting
- Operating time
±0.5 % of the set pick-up value
±5 % or ± 500 ms
9.2.1.12 Overpower (P>; 32O), underpower (P<; 32U) and reverse power (Pr; 32R)
protection
Table. 9.2.1.12 - 254. Technical data for the power protection functions.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Voltage inputs
U
L1
, U
L2
, U
L3
U
L12
, U
L23
(+ U
0
)
Calculated measurement
Three-phase active power
A
AQ
Q-C213
-C213
Instruction manual
Version: 2.04
347