Name
Description
Range
Step
Default
Zone1/2/3/4 Light 1
Enabled
Light detected in sensor channel 1 trips the zone.
0: Disabled
1: Enabled
-
0:
Disabled
Zone1/2/3/4 Light 2
Enabled
Light detected in sensor channel 2 trips the zone.
0: Disabled
1: Enabled
-
0:
Disabled
Zone1/2/3/4 Light 3
Enabled
Light detected in sensor channel 3 trips the zone.
0: Disabled
1: Enabled
-
0:
Disabled
Zone1/2/3/4 Light 4
Enabled
Light detected in sensor channel 4 trips the zone.
0: Disabled
1: Enabled
-
0:
Disabled
Zone1/2/3/4 Pres. 1
Enabled
Pressure detected in sensor channel 1 trips the zone.
0: Disabled
1: Enabled
-
0:
Disabled
Zone1/2/3/4 Pres. 2
Enabled
Pressure detected in sensor channel 2 trips the zone.
0: Disabled
1: Enabled
-
0:
Disabled
Zone1/2/3/4 Pres. 3
Enabled
Pressure detected in sensor channel 3 trips the zone.
0: Disabled
1: Enabled
-
0:
Disabled
Zone1/2/3/4 Pres. 4
Enabled
Pressure detected in sensor channel 4 trips the zone.
0: Disabled
1: Enabled
-
0:
Disabled
Zone1/2/3/4 DI Enabled
Arc protection option card digital input has to be active for
the zone to trip.
0: Disabled
1: Enabled
-
0:
Disabled
The pick-up activation of the function is not directly equal to the TRIP signal generation of the function.
The TRIP signal is allowed if the blocking condition is not active.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.3.14 - 135. Information displayed by the function.
Name
Range
Step
Description
I/I0 Arc> condition
0: Z1 Trip
1: Z1 Blocked
2: Z2 Trip
3: Z2 Blocked
4: Z3 Trip
5: Z3 Blocked
6: Z4 Trip
7:Z4 Blocked
-
Displays status of the protection function.
Sensor status
0: Ph Curr Blocked
1: Ph Curr Start
2: Res Curr Blocked
3: Res Curr Start
4: Channel1 Light
5: Channel1 Pressure
6: Channel2 Light
7: Channel2 Pressure
8: Channel3 Light
9: Channel3 Pressure
10: Channel4 Ligh
t11: Channel4 Pressure
12: Digital input
13: I/I0 Arc> Sensor 1 Fault
14: I/I0 Arc> Sensor 2 Fault
15: I/I0 Arc> Sensor 3 Fault
16: I/I0 Arc> Sensor 4 Fault
17: I/I0 Arc> I/O-unit Fault
-
Displays the general status of sensors.
A
AQ
Q-C213
-C213
Instruction manual
Version: 2.04
198
Содержание AQ-C213
Страница 1: ...AQ C213 Capacitor bank protection IED Instruction manual ...
Страница 308: ...Figure 7 4 184 Example block scheme A AQ Q C213 C213 Instruction manual Version 2 04 307 ...
Страница 330: ...Figure 8 14 207 Panel cutout dimensions and device spacing A AQ Q C213 C213 Instruction manual Version 2 04 329 ...