• SG loc
SG local select
al select: selects the local control for the different setting groups (can use digital
inputs, logical inputs or outputs, RTDs, object status information as well as stage starts, trips
or blocks).
• R
Remo
emotte se
e settting gr
ting group change
oup change: When enabled it is possible to change the setting group
manually through SCADA.
• SG e
SG evvents
ents: event masking for setting groups (masks are OFF by default; please note that only
masked events are recorded into the event history).
Setting group 1 (SG1) has the highest priority, while Setting group 8 (SG8) has the lowest priority.
Setting groups can be controlled with pulses or with both pulses and static signals (see the image
below).
Figure. 4.5 - 18. Example of setting group (SG) changing.
Objects
Figure. 4.5 - 19. Objects submenu.
Each activated object is visible in the
Objects submenu. By default all objects are disabled unless
specifically activated in the
Controls
→
Controls enabled submenu. Each active object has four
sections in their submenus: "Settings", "Application control" ("App contr"), "Registers" and "Events".
These are described in further detail below.
A
AQ
Q-C213
-C213
Instruction manual
Version: 2.04
25