Connections
Figure. 4.6 - 38. View of the Connections submenu.
The
Connections submenu offers the following bits of information and settings:
ETHERNET
ETHERNET
This section defines the IP settings for the ethernet port in the back panel of the unit.
• IP address: the IP address of the device which can be set by the user (the default IP address
depends on the device).
• Network: the network subnet mask is entered here.
• Gateway: the gateway is configured only when communicating with the devices in a separate
subnet.
• MAC-Address: Unique MAC address of the device. Not configurable by user.
SERIAL COM
SERIAL COM
This section defines the basic settings of RS-485 port in the back panel of the unit.
• Bitrate: displays the bitrate of the RS-485 serial communication interface (9600 bps as
standard, although can be changed to 19 200 bps or 38 400 bps if an external device
supports the faster speed).
• Databits, Parity and Stopbits: these can be set according the connected external devices.
• Protocol: by default the device does not have any serial protocol activated, although IEC
103, Modbus I/O and Modbus/RTU can be used for communication.
NO
NOTE!
TE!
When communicating with a device through a front Ethernet port connection, the IP address
is always 192.168.66.9.
SERIAL COM1 & COM2
SERIAL COM1 & COM2
SERIAL COM1 and SERIAL COM2 are reserved for serial communication option cards. They have the
same settings as RS-485 port.
A
AQ
Q-C213
-C213
Instruction manual
Version: 2.04
39