Control mode
Local
Any digital signal available in the device
Remote
Force change overrule of local controls either from the setting tool, HMI or SCADA
Operation time
Reaction time
<5 ms from receiving the control signal
9.2.2.2 Object control and monitoring
Table. 9.2.2.2 - 258. Technical data for the object control and monitoring function.
Signals
Input signals
Digital inputs
Software signals
Output signals
Close command output
Open command output
Operation time
Breaker traverse time setting
0.02…500.00 s, setting step 0.02 s
Max. close/open command pulse length
0.02…500.00 s, setting step 0.02 s
Control termination time out setting
0.02…500.00 s, setting step 0.02 s
Inaccuracy:
- Definite time operating time
±0.5 % or ±10 ms
Breaker control operation time
External object control time
<75 ms
Object control during auto-reclosing
See the technical sheet for the auto-reclosing function.
9.2.2.3 Switch-on-to-fault (SOTF)
Table. 9.2.2.3 - 259. Technical data for the switch-on-to-fault function.
Initialization signals
SOTF activate input
Any IED blocking input signal (Object closed signal, etc.)
Pick-up
SOTF function input
Any IED blocking input signal (I> or similar)
SOTF activation time
Activation time
<40 ms (measured from the trip contact)
SOTF release time
Release time setting
0.000…1800.000 s, setting step 0.005 s
Inaccuracy:
- Definite time
±1.0 % or ±30 ms
SOTF instant release time
<40 ms (measured from the trip contact)
A
AQ
Q-C213
-C213
Instruction manual
Version: 2.04
350