The function generates general time stamped ON/OFF events to the common event buffer from each of
the two (2) output signals as well as several operational event signals. The time stamp resolution is 1
ms. The function also provides a resettable cumulative counter for OPEN, CLOSE, OPEN FAILED, and
CLOSE FAILED events.
The following figure presents a simplified function block diagram of the object control and monitoring
function.
Figure. 5.4.2 - 148. Simplified function block diagram of the object control and monitoring function.
Settings
The following parameters help the user to define the object. The operation of the function varies based
on these settings and the selected object type. The selected object type determines how much control
is needed and which setting parameters are required to meet those needs.
Table. 5.4.2 - 146. Object set and status.
Name
Range
Step Default
Description
Local/Remote
status
0: Local
1: Remote
-
1:
Remote
Displays the status of the relay's "local/remote" switch. Local controls
cannot override the open and close commands while device is in
"Remote" status. The remote controls cannot override the open
and close commands while device is in "Local" status.
Object name
-
-
Objectx The user-set name of the object, at maximum 32 characters long.
Object type
0: Withdrawable
circuit breaker
1: Circuit
breaker
2: Disconnector
(MC)
3: Disconnector
(GND)
-
1:
Circuit
breaker
The selection of the object type. This selection defines the number of
required digital inputs for the monitored object. This affects the symbol
displayed in the HMI and the monitoring of the circuit breaker. It also
affects whether the withdrawable cart is in/out status is monitored. See
the next table ("Object types") for a more detailed look at which
functionalities each of the object types have.
Objectx
Breaker
status
0: Intermediate
1: Open
2: Closed
3: Bad
-
-
Displays the status of breaker. Intermediate is displayed when neither of
the status signals (open or close) are active. Bad status is displayed
when both status signals (open and close) are active.
Objectx
Withdraw
status
0:
WDIntermediate
1: WDCartOut
2: WDCart In
3: WDBad
4: Not in use
-
-
Displays the status of circuit breaker cart. WDIntermediate is displayed
when neither of the status signals (in or out) are active. WDBad status is
displayed when both status signals (in and out) are active. If the selected
object type is not set to "Withdrawable circuit breaker", this setting
displays the "No in use" option
.
A
AQ
Q-C213
-C213
Instruction manual
Version: 2.04
228
Содержание AQ-C213
Страница 1: ...AQ C213 Capacitor bank protection IED Instruction manual ...
Страница 308: ...Figure 7 4 184 Example block scheme A AQ Q C213 C213 Instruction manual Version 2 04 307 ...
Страница 330: ...Figure 8 14 207 Panel cutout dimensions and device spacing A AQ Q C213 C213 Instruction manual Version 2 04 329 ...