Operating time characteristics for trip and reset
The operating timers’ behavior during a function can be set for TRIP signal and also for the release of
the function in case the pick-up element is reset before the trip time has been reached. There are three
basic operating modes available for the function:
• Instant operation: gives the TRIP signal with no additional time delay simultaneously with the
START signal.
• Definite time operation (DT): gives the TRIP signal after a user-defined time delay regardless
of the measured or calculated voltage as long as the voltage is above the
U
set
value and
thus the pick-up element is active (independent time characteristics).
• Inverse definite minimum time (IDMT): gives the TRIP signal after a time which is in relation
to the set pick-up voltage
U
set
and the measured voltage
U
m
(dependent time
characteristics).
The IDMT function follows this formula:
Where:
•
t = operating time
•
k = time dial setting
•
U
m
= measured voltage
•
U
s
= pick-up setting
•
a = IDMT multiplier setting
The following table presents the setting parameters for the function's time characteristics.
Table. 5.3.10 - 105. Setting parameters for operating time characteristics.
Name
Range
Step
Default
Description
Delay type 1: DT
2: IDMT
-
1: DT
Selection of the delay type time counter. The selection possibilities are
dependent (IDMT, Inverse Definite Minimum Time) and independent
(DT, Definite Time) characteristics.
Definite
operating
time delay
0.000…1800.000s 0.005s 0.040s
Definite time operating delay. The setting is active and visible when DT
is the selected delay type.
When set to 0.000 s, the stage operates as instant without added delay.
When the parameter is set to 0.005...1800 s, the stage operates as
independent delayed.
Time dial
setting k
0.01…60.00s
0.01s
0.05s
The setting is active and visible when IDMT is the selected delay type.
Time dial/multiplier setting for IDMT characteristics.
IDMT
Multiplier
0.01…25.00s
0.01s
1.00s
The setting is active and visible when IDMT is the selected delay type.
IDMT time multiplier in the U
m
/U
set
power.
Table. 5.3.10 - 106. Setting parameters for reset time characteristics.
Name
Range
Step
Default
Description
Release
time delay
0.000…150.000s 0.005s 0.06s
Resetting time. Time allowed between pick-ups if the pick-up has not led
to a trip operation. During this time the START signal is held on for the
timers if the delayed pick-up release is active.
A
AQ
Q-C213
-C213
Instruction manual
Version: 2.04
159
Содержание AQ-C213
Страница 1: ...AQ C213 Capacitor bank protection IED Instruction manual ...
Страница 308: ...Figure 7 4 184 Example block scheme A AQ Q C213 C213 Instruction manual Version 2 04 307 ...
Страница 330: ...Figure 8 14 207 Panel cutout dimensions and device spacing A AQ Q C213 C213 Instruction manual Version 2 04 329 ...