CPS100 SERIES OPERATION MANUAL
SECTION 6:
Entire Contents Copyright
2018 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
APS CPS100 Series Power Source Operation Manual
Page 81 of 231
The following measurement parameters are available to choose from:
LABEL
MEASUREMENT
UNIT
LEFT COLUMN
V
Voltage (Vac+Vdc)
V
Vac
Voltage AC RMS
V
Vdc
Voltage DC
V
Vpk
Peak-to-Peak Voltage
V
VAR
Reactive Power
VAR
CENTER COLUMN
I
Total Current (Iac + Idc)
A
Iac
AC Current RMS
A
Idc
DC Current
A
Ipk
Peak Current
A
Is
Surge Current
A
RIGHT COLUMN
P
True Power
W
PF
Power Factor (P / VA)
VA
Apparent Power ( VA = P + VAR)
VA
CF
Crest Factor (Ipk / I)
F
Frequency
Hz
Table 6-2: Available Measurements and Units
The following four Soft keys are available in the Measurement Settings screen:
•
I Range
•
Average
•
Is Delay
•
Is Interval
6.7.2.1 I Range Setting
The I Range soft key allows selection of the
current measurement range. Available settings
are:
•
High
•
Middle
•
Low
•
Auto
•
mA
Actual measurement ranges of each of these settings may vary by model. Consult the
Technical data section for data by model.
To select a current range, press the I Range soft key and select a range from the available
list.
Note:
The
Auto
Range selection will only switch between High and Middle ranges. To
change settings between High/Middle and Low/mA ranges, the power source must
be turned off first.