CPS100 SERIES OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
APS CPS100 Series Power Source Operation Manual
Page 175 of 231
Move the cursor position to the Mode field
in the top part of the screen.
Available unit modes are:
•
Single
Stand-alone operation
•
Master Master unit
•
Slave
Slave unit
From the drop down list, select the
Slave
entry and press the [Enter] key to confirm.
The
Slave Type =
field will now be visible.
The maximum number of slaves is three for
parallel mode. For three phase mode, two
slaves (Slave1 & Slave2) are required.
For Series mode, there can only be one Slave
so Slave1 must be selected.
Note:
For series operation of two units, the
Slave Type setting
MUST
be set to
Slave1.
Next, press the Set soft key to save the Mode
and Slave type selection. This will lock this
power source into Slave mode.
Note:
The Slave unit can also be unlocked
using the [.] key on the front panel.
Now press the Load soft key to load and
display the saved settings for this slave unit.
Finally, press the Save soft key to store the
Master-Slave mode setting to non-volatile
memory. This unit is now ready to be used in
a Master/Slave configuration. Slave units will
keep their output
OFF
as they are controlled
by the Master unit.
Note:
NEVER change the connections and modes of Master and Slave units while in multi-
unit mode operation as it could damage one of more units.