CPS100 SERIES OPERATION MANUAL
SECTION 5:
Entire Contents Copyright
2018 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
APS CPS100 Series Power Source Operation Manual
Page 47 of 231
5.4.3
Input Power Cord Installation
To install a power cord to the AC input terminal block, proceed as follows:
1.
Strip the outside installation of the AC power cord approximately 25 mm or 1 inch.
Then strip 7 mm or 1/3 inch of insulation from each of the wires (L, N, G) of the
power cord.
2.
Loosen the plastic nut of the provided
input safety cover’s stain relief.
3.
Pass the cable end including the line,
neutral and ground wire through the
cable strain relief as illustrated in the
adjacent drawing.
4.
Insert each lead in its corresponding
input terminal position as shown.
5.
Using a suitable size flat blade
screwdriver, tighten the terminal block
screws assuring all wires are held
tightly.
6.
Replace and faster the safety cover and
tighten the plastic nut of the strain
relief clamp.
5.4.4
Grounding Requirements
WARNING
SHOCK HAZARD
EQUIPMENT MUST BE GROUNDED
The chassis must be grounded. A proper Earth Ground connection must be used at all times.
Correct grounding of your electrical system infrastructure according to applicable national
standards must be observed.