CPS100 SERIES OPERATION MANUAL
SECTION 5:
Entire Contents Copyright
2018 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
APS CPS100 Series Power Source Operation Manual
Page 46 of 231
5.4.1
AC Input Wire Sizes by Model
Model
Wire Size
Input
Breaker
Model
Wire Size
Input
Breaker
CPS106
2.0 mm
2
/ 16 AWG
12 A
CPS130
3.5 mm
2
/ 12 AWG
25 A
CPS110
2.5 mm
2
/ 14 AWG
16 A
CPS140
5.6 mm
2
/ 10 AWG
30 A
CPS150
3.5 mm
2
/ 12 AWG
20 A
CPS150
8.5 mm
2
/ 8 AWG
40 A
CPS120
3.5 mm
2
/ 12 AWG
20 A
Table 5-2: AC Input Wire Sizes by Model
Note:
Breaker ratings shown for CPS106 through CPS115 are for 115V~. Breaker ratings
shown for CPS120 through CPS150 are for 230V~.
5.4.2
AC Input Terminal as Safety Cover
The AC input connections are made at the rear of the CPS100 units. The AC input terminal is
located on the right hand side when facing the back panel of the power source.
A safety cover is provided for both AC input and AC/DC Output terminal blocks.
CAUTION
The included AC Input and Output safety covers must be
properly installed when using this equipment