Appendix
255
Omit All
Yes
Quick Set
No
This setting is required to fulfil
EN50131.
Quick Omit
No
User Code Req’d
Yes
This setting is required to fulfil
EN50131.
EN50131-1, Section 8.3.1 (with ref-
erence to EN50131-3, Section 8.3.1)
2 Way Replies
Yes
Remote Inst. Set
Yes
Duress Enable
No
Switch to Yes for Duress Code use
User Reset
Zone Alarms
Yes
This option only appears if the con-
firmation mode is set to "Basic".
Zone Tampers
Yes
For INCERT detection, set to NO.
System Tampers
No
Confirmation
Confirmation mode
Basic
Default for systems apart from the
UK
This value depends on how you an-
swer the "
Country defaults
" question
during initial commissioning.
DD243
BS8243
Default for UK systems if the UK is
chosen as the country.
This value depends on how you an-
swer the "
Country defaults
" question
during initial commissioning.
Confirmation time
30 minutes
Visible for DD243 or BS8243.
Can be set to between 1 and
60 minutes. Ensure that only one
value of 30 minutes or more is com-
pliant with DD243 or BS8243.
After Entry
1 Zone
Visible for DD243 or BS8243. The
default setting is changed to 2 zones
if the confirmation mode = DD243.
Entry Keypad Lock
Off
Visible for DD243 or BS8243.
Sounder On
Unconfirm
Visible for DD243, BS8243 and
Basic.
Siren On
Unconfirm
Visible for DD243, BS8243 and
Basic.
Unconfirmed Reset
User
Visible for DD243 or BS8243.
Confirmed Reset
Installer
Visible for DD243 or BS8243.
Hold Up Alarm confirma-
tion time
8 hours
Only visible for BS8243. Must be be-
tween 8 and 20 hours to be compli-
ant with BS8243:2010.
Tamp as Tamp-Only
Enabled
Visible for BS8243.
Hardware
Wired Zone Type
2-wire FSL 2K2/4K7
This value depends on how you an-
swer the "
Wired Zone Type
" ques-
tion during initial commissioning.
RF Siren Options
Siren + Strobe
Battery 2
Disabled
SD Card
GSM/mobile antenna
Internal
Содержание SECVEST FUAA50 Series
Страница 12: ...Device overview 12 International key assignment...
Страница 39: ...Configuration 39 Communication...
Страница 46: ...Configuration 46 Components Teach in via web interface...
Страница 74: ...Configuration 74 Outputs...
Страница 85: ...Configuration 85 1 Select menu item Type...
Страница 94: ...Configuration 94...
Страница 111: ...Configuration 111 System...
Страница 118: ...Configuration 118 A user can reset the alarm and the General Fault outputs after entering their user code...
Страница 148: ...Configuration 148 Communication Network...
Страница 157: ...Configuration 157 ARC reporting...
Страница 159: ...Configuration 159...
Страница 177: ...Configuration 177 Voice dialler S W 3 00 05...
Страница 185: ...Configuration 185...
Страница 216: ...Configuration 216...
Страница 229: ...Configuration 229 Log S W v2 01 08...
Страница 278: ...Appendix 278...
Страница 326: ......