Configuration
119
Name/function
Explanation (checkbox)
Ext DC Fault Reporting
Enabled
Reports that a fault has occurred with the external DC power supply.
Deactivated
Function not possible.
Ext DC Fault Delay
(minutes)
Delay time in minutes (0
–60 minutes) until the message is sent.
If a DC Fault occurs the alarm panel displays an error message after a few sec-
onds, "General Fault" outputs activate and a log book entry is created (Mandatory
Events).
Power disruptions that last less than 9 s are not reported.
If the power supply is restored within these 9 seconds, the "General Fault" outputs
are reset and a log book entry is created: "Power supply restored".
If the power disruption lasts longer than 9 s, the following occurs:
If the value is set to 0 min, a warning tone is sounded after 10 s and the alarm
panel reports the failure. "DC Fault" outputs are activated.
If the value is set to higher than 0 min, this timer is started 10 s after the disruption
occurs.
If the power supply is restored before the end of the set delay time, "General Fault"
outputs are reset and a log book entry is created about the power restore.
No errors are reported.
If the fault still exists after the end of the configured time, a warning tone sounds
and the error is reported. "DC Fault" outputs are activated.
A user can stop the warning tone by entering their code. The alarm panel display
shows details of the warning. "General Fault" and "DC Fault" outputs remain acti-
vated.
If the fault has been corrected, the alarm panel deactivates the "DC Fault" outputs
and creates a log book entry about the power restore. A user can reset the alarm
and the "General Fault" outputs after entering their user code.
Содержание SECVEST FUAA50 Series
Страница 12: ...Device overview 12 International key assignment...
Страница 39: ...Configuration 39 Communication...
Страница 46: ...Configuration 46 Components Teach in via web interface...
Страница 74: ...Configuration 74 Outputs...
Страница 85: ...Configuration 85 1 Select menu item Type...
Страница 94: ...Configuration 94...
Страница 111: ...Configuration 111 System...
Страница 118: ...Configuration 118 A user can reset the alarm and the General Fault outputs after entering their user code...
Страница 148: ...Configuration 148 Communication Network...
Страница 157: ...Configuration 157 ARC reporting...
Страница 159: ...Configuration 159...
Страница 177: ...Configuration 177 Voice dialler S W 3 00 05...
Страница 185: ...Configuration 185...
Страница 216: ...Configuration 216...
Страница 229: ...Configuration 229 Log S W v2 01 08...
Страница 278: ...Appendix 278...
Страница 326: ......