Configuration
225
Role
Meaning
Zone Resistances
The current resistances for the wired zones are displayed here.
Display on the alarm panel:
The zone names are displayed. To view the zone numbers, press the right menu key.
Test all variants according to the type of wiring to determine whether they meet the require-
ments:
Alarm contact open/closed
Tamper contact open/closed
Short circuits
Open (isolated circuits)
0k00 means 0 ohms or NC
For wiring type "4-wire CC" the display switches between the resistance of the
alarm loop (A) and the resistance of the tamper loop (S).
Example for a "2-wire FSL 2K2/4K7" zone
Alarm contact closed (standby)
2k18
Alarm contact open
6k89
Alarm contact open and series resistor bridged
4k68
Short circuit in line to detector
0k00
Line disconnection
NO
Panel PSU
Here you can find information about the voltage values of the power supply. The display is
identical on the alarm panel and the web interface.
Ext. DC voltage in
The voltage value of the external DC power source
Panel Battery 1
The voltage value of the first battery
Panel Battery 2
The voltage value of the second battery
Aux. Voltage Out
The voltage value at the terminal clamp 0 V/12 V AUX
Example
(battery 2 is not connected in this example)
Ext. DC voltage in
14.1 volts
Panel Battery 1
8.3 volts
Panel Battery 2
0.1 volts
Aux. Voltage Out
13.9 volts
RF repeater
Here you can find information about the signal strength of the components on the re-
peater.
This is the signal strength on the repeater of the received notifications from the com-
ponents. The display is identical on the alarm panel and the web interface
Содержание SECVEST FUAA50 Series
Страница 12: ...Device overview 12 International key assignment...
Страница 39: ...Configuration 39 Communication...
Страница 46: ...Configuration 46 Components Teach in via web interface...
Страница 74: ...Configuration 74 Outputs...
Страница 85: ...Configuration 85 1 Select menu item Type...
Страница 94: ...Configuration 94...
Страница 111: ...Configuration 111 System...
Страница 118: ...Configuration 118 A user can reset the alarm and the General Fault outputs after entering their user code...
Страница 148: ...Configuration 148 Communication Network...
Страница 157: ...Configuration 157 ARC reporting...
Страница 159: ...Configuration 159...
Страница 177: ...Configuration 177 Voice dialler S W 3 00 05...
Страница 185: ...Configuration 185...
Страница 216: ...Configuration 216...
Страница 229: ...Configuration 229 Log S W v2 01 08...
Страница 278: ...Appendix 278...
Страница 326: ......