Configuration
55
Selecting a partition
Note
The taught-in detectors are assigned to
Partition
01
by
default
.
To assign the detector to another partition, pro-
ceed as follows:
1. Use the checkboxes to select the desired
parti-
tion(s)
in which this zone will be monitored.
Note
At least one partition must be selected.
A settings option for the partitions can be found in the
section "Configuring Secvest via web server -> Partitions"
in this guide.
Zones of the following types can be assigned to one
or more partitions: Normal Alarm, Zone Lock, Final
Door, Entry Route, Key Switch, Key Box, Log Only,
Exit Terminate, Lock Set and Exit Norm Alm.
Note
If you plan on using internally armed partitions,
you must ensure that the internally armed options
are the same for all zones used for more than one
partition.
The wireless alarm panel does not allow zones of
the following types to be assigned to more than
one partition: 24 Hour Alarm, Fire Alarm, Hold Up
Alarm, Perimeter Warning, Tamper and Technical
Alarm.
Selecting zone attributes
1. Use the checkboxes to select the desired
attrib-
ute(s)
.
Attribute
Explanation
Chime
Each time this zone is triggered when the
alarm panel is disarmed, the panel
sounds an acoustic signal.
Force Set
Omit
If a zone is given this attribute, this zone
is automatically omitted if it was open
when the system was armed.
Attribute
Explanation
Omittable
If a zone is given this attribute, a user can
omit this zone before arming the system.
If a user attempts to arm the system when
a zone with this attribute is open, a warn-
ing appears and the arming process is in-
terrupted.
The user can acknowledge this warning
and continue the arming process.
Dis. Sabo-
tage
This attribute is an additional attribute for
mechatronic ABUS door and window
locks. The "Normal Alarm" zone type must
be selected.
When the "Dis. Sabotage" attribute is se-
lected, pry-attempt monitoring of the sup-
ported mechatronic products is switched
off when the alarm system is disarmed.
This attribute is not recommended and is
only necessary is special cases.
A "W" appears in the attribute line on the
alarm panel display.
Soak Test
If a detector tends to trigger a false alarm,
activate the soak test.
This setting resets automatically after
14 days.
The detector
does not trigger any
alarms
on the alarm panel during this
time.
However, all triggers are written to the
memory (log book) for analysis purposes.
Note
If the zone is triggered within these 14
days when the system is activated, the
arming of system will log the event as
“soak test fault Znnn alarm” (nnn is the
zone number). No sirens will be actuated
or communications started.
If the alarm panel is deactivated, the dis-
play will show a triangular symbol to in-
form the user. An
installer
must enter
their access code
to reset the alarm.
When activated, the display will show a
short message to inform the user that one
or more zones are in the soak test.
You can use this attribute for the following
zone types: Normal alarms,
entry route and tamper.
Part
Set
This zone is monitored when the partition
of this zone or all partitions are internally
armed.
Содержание SECVEST FUAA50 Series
Страница 12: ...Device overview 12 International key assignment...
Страница 39: ...Configuration 39 Communication...
Страница 46: ...Configuration 46 Components Teach in via web interface...
Страница 74: ...Configuration 74 Outputs...
Страница 85: ...Configuration 85 1 Select menu item Type...
Страница 94: ...Configuration 94...
Страница 111: ...Configuration 111 System...
Страница 118: ...Configuration 118 A user can reset the alarm and the General Fault outputs after entering their user code...
Страница 148: ...Configuration 148 Communication Network...
Страница 157: ...Configuration 157 ARC reporting...
Страница 159: ...Configuration 159...
Страница 177: ...Configuration 177 Voice dialler S W 3 00 05...
Страница 185: ...Configuration 185...
Страница 216: ...Configuration 216...
Страница 229: ...Configuration 229 Log S W v2 01 08...
Страница 278: ...Appendix 278...
Страница 326: ......