91
Actual signals and parameters
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
1104
REF1 MIN
Defines the minimum value for external reference REF1. Corresponds to the
minimum setting of the used source signal.
0.0 Hz
0.0
…500.0 Hz
Minimum value.
Example: Analog input AI1 is selected as the reference source (value of
parameter
1103
REF1 SELECT is AI1). The reference minimum and
maximum correspond to the
1301
MINIMUM AI1 and
1302
MAXIMUM AI1
settings as follows:
REF
(Hz)
REF
(Hz)
1104
1105
(MIN)
(MAX)
1104
1105
(MIN)
AI1 signal
(%) (MAX)
AI1 signal
(%)
1301
1302
1301
1302
1105
REF1 MAX
Defines the maximum value for external reference REF1. Corresponds to the
maximum setting of the used source signal.
E: 50.0 Hz /
U: 60.0 Hz
0.0
…500.0 Hz
Maximum value. See the example for parameter
1104
REF1 MIN.
1106
REF2 SELECT
Selects the signal source for external reference REF2.
2 = POT
0 = KEYPAD
See parameter
1103
REF1 SELECT.
1 = AI1
See parameter
1103
REF1 SELECT.
2 = POT
See parameter
1103
REF1 SELECT.
3 = AI1/JOYST
See parameter
1103
REF1 SELECT.
5 = DI3U,4D(R)
See parameter
1103
REF1 SELECT.
6 = DI3U,4D
See parameter
1103
REF1 SELECT.
11 = DI3U,4D(RNC)
See parameter
1103
REF1 SELECT.
12 = DI3U,4D(NC)
See parameter
1103
REF1 SELECT.
14 = AI1+POT
See parameter
1103
REF1 SELECT.
16 = AI1-POT
See parameter
1103
REF1 SELECT.
19 = PID1OUT
PID controller 1 output. See parameter group
40 PROCESS PID SET 1
.
30 = DI4U,5D
See parameter
1103
REF1 SELECT.
31 = DI4U,5D(NC)
See parameter
1103
REF1 SELECT.
32 = FREQ INPUT
See parameter
1103
REF1 SELECT.
1107
REF2 MIN
Defines the minimum value for external reference REF2. Corresponds to the
minimum setting of the used source signal.
0.0%
0.0
…100.0%
Value in percent of the maximum frequency. See the example for parameter
1104
REF1 MIN for correspondence to the source signal limits.
1108
REF2 MAX
Defines the maximum value for external reference REF2. Corresponds to the
maximum setting of the used source signal.
100.0%
0.0
…100.0%
Value in percent of the maximum frequency. See the example for parameter
1104
REF1 MIN for correspondence to the source signal limits.
1109
LOC REF SOURCE
Selects the source for the local reference.
0 = POT
0 = POT
Potentiometer
1 = KEYPAD
Control panel
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...