Actual signals and parameters
120
4007 value
Entry
Display
0
00003
3
1
00031
3.1
2
00314
3.14
3
03142
3.142
4
31416
3.1416
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
4004
PID DERIV FILTER
Defines the filter time constant for the derivative part of the process PID
controller. Increasing the filter time smooths the derivative and reduces
noise.
1.0 s
0.0
…10.0 s
Filter time constant. If parameter value is set to zero, the derivative filter is
disabled.
4005
ERROR VALUE INV
Selects the relationship between the feedback signal and drive speed (drive
output frequency).
0 = NO
0 = NO
Normal: A decrease in feedback signal increases drive speed (drive output
frequency). Error = Ref - Fbk
1 = YES
Inverted: A decrease in feedback signal decreases drive speed (drive output
frequency). Error = Fbk - Ref
4006
UNITS
Selects the unit for PID controller actual values.
4 = %
0
…12
See parameter
3405
OUTPUT1 UNIT selecti
ons 0…12 (NO UNIT…mV).
4007
UNIT SCALE
Defines the decimal point location for the display parameter selected by
parameter
4006
UNITS.
1
0
…4
Example PI (3.14159)
4008
0% VALUE
Defines together with parameter
4009
100% VALUE the scaling applied to
the PID controller
’s actual values.
Units
(4006)
Scale
(4007)
+1000%
4009
4008
Internal scale
(%)
0%
100%
-1000%
0
x…x
Unit and range depend on the unit and scale defined by parameters
4006
UNITS and
4007
UNIT SCALE.
4009
100% VALUE
Defines together with parameter
4008
0% VALUE the scaling applied to the
PID controller
’s actual values.
100
x...x
Unit and range depend on the unit and scale defined by parameters
4006
UNITS and
4007
UNIT SCALE.
4010
SET POINT SEL
Selects the source for the process PID controller reference signal.
2 = POT
0 = KEYPAD
Control panel
1 = AI1
Analog input AI1
2 = POT
Potentiometer
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...