Technical data
145
EMC compatibility and motor cable length
To comply with the European EMC Directive (standard IEC/EN 61800-3), use the following
maximum motor cable lengths for 4 kHz switching frequency.
All frame
sizes
Maximum motor cable length, 4 kHz
m
ft
With internal EMC filter
Second environment
(category C3
1)
)
30
100
First environment
(category C2
1)
)
-
-
First environment
(category C1
1)
)
-
-
With optional external EMC filter
Second environment
(category C3
1)
)
30 (at least)
2)
100 (at least)
2)
First environment
(category C2
1)
)
30 (at least)
2)
100 (at least)
2)
First environment
(category C1
1)
)
10 (at least)
2)
30 (at least)
2)
1)
See the new terms in section
Definitions
on page
148
.
2)
Maximum motor cable length is determined by the drive
’s operational factors. Contact your local
ABB representative for the exact maximum lengths when using external EMC filters
Note 1:
In multimotor systems, the calculated sum of all motor cable lengths must not
exceed the maximum motor cable length given in the table.
Note 2:
The internal EMC filter must be disconnected by removing the EMC screw (see
section
Connection procedure
on page
42
) while using an external EMC filter.
Note 3:
Radiated emissions are according to C2 with and without an external EMC filter.
Note 4
: Category C1 with conducted emissions only. Radiated emissions are not
compatible when measured with standard emission measurement setup and should be
checked or measured on cabinet and machine installations case by case.
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...