82
Actual signals and parameters
Parameters in the Short parameter mode
No.
Name/Value
Description
Def
12 CONSTANT SPEEDS
Constant speeds. Constant speed activation overrides the external speed
reference. Constant speed selections are ignored if drive is in the local
control mode.
As default constant speed selection is made through digital inputs DI3 and
DI4.1 = DI active, 0 = DI inactive.
DI3
DI4
Operation
0
0
No constant speed
1
0
Speed defined by parameter
1202
CONST SPEED 1
0
1
Speed defined by parameter
1203
CONST SPEED 2
1
1
Speed defined by parameter
1204
CONST SPEED 3
1202
CONST SPEED 1
Defines constant speed 1 (that is drive output frequency).
E: 5.0 Hz /
U: 6.0 Hz
0.0
…500.0 Hz
Output frequency
1203
CONST SPEED 2
Defines constant speed 2 (that is drive output frequency).
E: 10.0 Hz /
U: 12.0 Hz
0.0
…500.0 Hz
Output frequency
1204
CONST SPEED 3
Defines constant speed 3 (that is drive output frequency).
E: 15.0 Hz /
U: 18.0 Hz
0.0
…500.0 Hz
Output frequency
13 ANALOG INPUTS
Analog input signal minimum
1301
MINIMUM AI1
Defines the minimum % value that corresponds to minimum mA/(V) signal for
analog input AI1.
0...20 mA = 0...100%
4...20 mA = 20...100%
When analog input AI1 is selected as the source for external reference
REF1, the value corresponds to the minimum reference value, that is 0 Hz.
See the figure for parameter
1105
REF1 MAX.
0%
0
…100.0%
Value in percent of the full signal range. Example: If the minimum value for
analog input is 4 mA, the percent value for
0…20 mA range is:
(4 mA / 20 mA) · 100% = 20%
20 LIMITS
Maximum frequency
2008
MAXIMUM FREQ
Defines the maximum limit for the drive output frequen
cy.
t
E: 50.0 Hz /
U: 60.0 Hz
f
2008
0
-(2008)
Allowed frequency range
0.0
…500.0 Hz
Maximum frequency
21 START/STOP
Stop mode of the motor
2102
STOP FUNCTION
Selects the motor stop function.
1 = COAST
1 = COAST
Stop by cutting off the motor power supply. The motor coasts to stop.
2 = RAMP
Stop along a linear ramp. See parameter group
22 ACCEL/DECEL
.
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...