Fault tracing
Alarm messages generated by the drive
CODE
ALARM
CAUSE
WHAT TO DO
A2001
OVERCURRENT
(programmable fault
function, parameter
1610
DISPLAY
ALARMS)
Output current limit controller is
active.
Check motor load.
Check acceleration time (parameters
2202
ACCELER TIME 1 and
2205
ACCELER
TIME 2).
Check motor and motor cable (including
phasing).
Check ambient conditions. Load capacity
decreases if installation site ambient
temperature exceeds 40 °C. See section
Derating
on page
138
.
A2002
OVERVOLTAGE
(programmable fault
function, parameter
1610
DISPLAY
ALARMS)
DC overvoltage controller is
active.
Check deceleration time (parameters
2203
DECELER TIME 1 and
2206
DECELER
TIME 2).
Check input power line for static or transient
overvoltage.
A2003
UNDERVOLTAGE
(programmable fault
function, parameter
1610
DISPLAY
ALARMS)
DC undervoltage controller is
active.
Check input power supply.
A2004
DIRLOCK
Change of direction is not
allowed.
Check parameter
1003
DIRECTION
settings.
A2006
AI1 LOSS
(programmable fault
function, parameters
3001
AI<MIN
FUNCTION,
3021
AI1
FAULT LIMIT)
Analog input AI1 signal has fallen
below limit defined by parameter
3021
AI1 FAULT LIMIT.
Check fault function parameter settings.
Check for proper analog control signal
levels.
Check connections.
A2009
DEVICE OVERTEMP
Drive IGBT temperature is
excessive. Alarm limit is 120 °C.
Check ambient conditions. See also section
Derating
on page
138
.
Check air flow and fan operation.
Check motor power against drive power.
A2010
MOTOR TEMP
(programmable fault
function, parameters
3005
...
3009
)
Motor temperature is too high (or
appears to be too high) due to
excessive load, insufficient motor
power, inadequate cooling or
incorrect start-up data.
Check motor ratings, load and cooling.
Check start-up data.
Check fault function parameter settings.
Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
A2011
UNDERLOAD
(programmable fault
function, parameters
3013
...
3015
)
Motor load is too low due to, for
example, release mechanism in
driven equipment.
Check for problem in driven equipment.
Check fault function parameter settings.
Check motor power against drive power.
A2012
MOTOR STALL
(programmable fault
function, parameters
3010
...
3012
)
Motor is operating in stall region
due to, for example, excessive
load or insufficient motor power.
Check motor load and drive ratings.
Check fault function parameter settings.
A2013
1)
AUTORESET
Automatic reset alarm
Check parameter group
31 AUTOMATIC
RESET
settings.
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...