Actual signals and parameters
105
P
N
(kW)
0.37
0.75
2.2
4.0
200…240
V units
IR comp (V)
8.4
7.7
5.6
8.4
380…480
V units
IR comp (V)
14
14
5.6
8.4
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
26 MOTOR CONTROL
Motor control variables
2601
FLUX OPT ENABLE
Activates/deactivates the Flux optimisation function. Flux optimisation
reduces the total energy consumption and motor noise level when the drive
operates below the nominal load. The total efficiency (motor and the drive)
can be improved by 1% to 10%, depending on the load torque and speed.
The disadvantage of this function is that the dynamic performance of the
drive is weakened.
0 = OFF
0 = OFF
Inactive
1 = ON
Active
2603
IR COMP VOLT
Defines the output voltage boost at zero speed (IR compensation). The
function is useful in applications with a high break-away torque. To prevent
overheating, set IR compensation voltage as low as possible.
The figure below illustrates the IR compensation.
Motor
A = IR compensated
voltage
B = No compensation
A
Typical IR compensation values:
2603
f
(Hz)
B
2604
Type
dependent
0.0
…100.0 V
Voltage boost
2604
IR COMP FREQ
Defines the frequency at which the IR compensation is 0 V. See the figure for
parameter
2603
IR COMP VOLT.
80%
0...100%
Value in percent of the motor frequency
2605
U/F RATIO
Selects the voltage to frequency (U/f) ratio below the field weakening point.
1 = LINEAR
1 = LINEAR
Linear ratio for constant torque applications
2 = SQUARED
Squared ratio for centrifugal pump and fan applications. With squared U/f
ratio the noise level is lower for most operating frequencies.
2606
SWITCHING FREQ
Defines the switching frequency of the drive. Higher switching frequency
results in lower acoustic noise. See also parameter
2607
SWITCH FREQ
CTRL and section
Switching frequency derating, I2N
on page
139
.
In multimotor systems, do not change the switching frequency from the
default value.
4 kHz
4 kHz
4 kHz
8 kHz
8 kHz
12 kHz
12 kHz
16 kHz
16 kHz
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...