Technical data
140
Power cable sizes and fuses
Cable dimensioning for rated currents (
I
1N
) is shown in the table below together with
the corresponding fuse types for short-circuit protection of the input power cable.
The rated fuse currents given in the table are the maximums for the mentioned
fuse types. If smaller fuse ratings are used, check that the fuse rms current
rating is larger than the rated
I
1N
current given in section
Ratings
on page
137
.
If 150% output power is needed, multiply current
I
1N
by 1.5. See also section
Selecting the power cables
on page
30
.
Check that the operating time of the fuse is below 0.5 seconds
. The operating
time depends on the fuse type, the supply network impedance as well as the cross-
sectional area, material and length of the supply cable. In case the 0.5 seconds
operating time is exceeded with the gG or T fuses, ultra rapid (aR) fuses in most
cases reduce the operating time to an acceptable level.
Note:
Larger fuses must not be used when the input power cable is selected according to this table.
Type
ACS150-
x = E/U
Fuses
Size of CU conductor in cablings
gG
UL Class
T (600 V)
Supply
(U1, V1, W1)
Motor
(U2, V2, W2)
PE
Brake
(BRK+ and BRK-)
A
A
mm
2
AWG
mm
2
AWG
mm
2
AWG
mm
2
AWG
1-phase
U
N
= 200
…240 V
(200, 208, 220, 230, 240 V)
01x-02A4-2
10
10
2.5
14
0.75
18
2.5
14
2.5
14
01x-04A7-2
16
20
2.5
14
0.75
18
2.5
14
2.5
14
01x-06A7-2
16/20
1)
25
2.5
10
1.5
14
2.5
10
2.5
12
01x-07A5-2
20/25
1)
30
2.5
10
1.5
14
2.5
10
2.5
12
01x-09A8-2
25/35
1)
35
6
10
2.5
12
6
10
6
12
3-phase
U
N
= 200
…240 V
(200, 208, 220, 230, 240 V)
03x-02A4-2
10
10
2.5
14
0.75
18
2.5
14
2.5
14
03x-03A5-2
10
10
2.5
14
0.75
18
2.5
14
2.5
14
03x-04A7-2
10
15
2.5
14
0.75
18
2.5
14
2.5
14
03x-06A7-2
16
15
2.5
12
1.5
14
2.5
12
2.5
12
03x-07A5-2
16
15
2.5
12
1.5
14
2.5
12
2.5
12
03x-09A8-2
16
20
2.5
12
2.5
12
2.5
12
2.5
12
3-phase
U
N
= 380
…480 V
(380, 400, 415, 440, 460, 480 V)
03x-01A2-4
10
10
2.5
14
0.75
18
2.5
14
2.5
14
03x-01A9-4
10
10
2.5
14
0.75
18
2.5
14
2.5
14
03x-02A4-4
10
10
2.5
14
0.75
18
2.5
14
2.5
14
03x-03A3-4
10
10
2.5
12
0.75
18
2.5
12
2.5
12
03x-04A1-4
16
15
2.5
12
0.75
18
2.5
12
2.5
12
03x-05A6-4
16
15
2.5
12
1.5
14
2.5
12
2.5
12
03x-07A3-4
16
20
2.5
12
1.5
14
2.5
12
2.5
12
03x-08A8-4
20
25
2.5
12
2.5
12
2.5
12
2.5
12
00353783.xls J
1)
If 50% overload capacity is needed, use the larger fuse alternative.
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...