98
Actual signals and parameters
2007 value is < 0
Allowed frequency range
Parameters in the Long parameter mode
Index Name/Selection
Description
Def
18 FREQ INPUT
Frequency input signal processing. Digital input DI5 can be programmed as
a frequency input. Frequency input can be used as external reference signal
source. See parameter
1103
/
1106
REF1/2 SELECT.
1801 FREQ INPUT MIN
Defines the minimum input value when DI5 is used as a frequency input.
0 Hz
0
…16000 Hz
Minimum frequency
1802 FREQ INPUT MAX
Defines the maximum input value when DI5 is used as a frequency input.
1000 Hz
0
…16000 Hz
Maximum frequency
1803 FILTER FREQ IN
Defines the filter time constant for frequency input, that is the time within
which 63% of a step change is reached.
0.0
…10.0 s
Filter time constant
20 LIMITS
Drive operation limits
0.1 s
2003 MAX CURRENT
Defines the allowed maximum motor current.
1.8 ·
I
2N
A
0.0
…1.8 ·
I
2N
A
Current
2005
OVERVOLT CTRL
Activates or deactivates the overvoltage control of the intermediate DC link.
Fast braking of a high inertia load causes the voltage to rise to the
overvoltage control limit. To prevent the DC voltage from exceeding the limit,
the overvoltage controller automatically decreases the braking torque.
Note:
If a brake chopper and resistor are connected to the drive, the
controller must be off (selection DISABLE) to allow chopper operation.
0 = DISABLE
Overvoltage control deactivated
1 = ENABLE
Overvoltage control activated
2006
UNDERVOLT CTRL
Activates or deactivates the undervoltage control of the intermediate DC link.
If the DC voltage drops due to input power cut off, the undervoltage controller
automatically decreases the motor speed in order to keep the voltage above
the lower limit. By decreasing the motor speed, the inertia of the load causes
regeneration back into the drive, keeping the DC link charged and preventing
an undervoltage trip until the motor coasts to stop. This acts as a power-loss
ride-through functionality in systems with a high inertia, such as a centrifuge
or a fan.
0 = DISABLE
Undervoltage control deactivated
1 = ENABLE(TIME)
Undervoltage control activated. The undervoltage control is active for
500 ms.
2 = ENABLE
Undervoltage control activated. No operation time limit.
2007 MINIMUM FREQ
Defines the minimum limit for the drive output frequency. A positive (or zero)
minimum frequency value defines two ranges, one positive and one negative.
A negative minimum frequency value defines one speed range.
Note:
MINIMUM FREQ value must not exceed MAXIMUM FREQ value.
1 = ENABLE
1 = ENABLE
(TIME)
0.0 Hz
f
2008
f
2008
2007
2007 value is > 0
Allowed frequency range
0
0
2007
t
-(2007)
-(2008)
t
Allowed frequency range
-5
00.0…500.0 Hz
Minimum frequency
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...