Actual signals and parameters
123
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
4019
ACT1 MAXIMUM
Defines the maximum value for the variable ACT1 if an analog input is
selected as a source for ACT1. See parameter
4016
ACT1 INPUT. The
minimum (
4018
ACT1 MINIMUM) and maximum settings of ACT1 define how
the voltage/current signal received from the measuring device is converted to
a percentage value used by the process PID controller.
See parameter
4018
ACT1 MINIMUM.
100%
-10
00…1000%
Value in percent
4020
ACT2 MINIMUM
See parameter
4018
ACT1 MINIMUM.
0%
-10
00…1000%
See parameter
4018
ACT1 MINIMUM.
4021
ACT2 MAXIMUM
See parameter
4019
ACT1 MAXIMUM.
100%
-10
00…1000%
See parameter
4019
ACT1 MAXIMUM.
4022
SLEEP SELECTION
Activates the sleep function and selects the source for the activation input.
0 = NOT SEL
0 = NOT SEL
No sleep function selected
1 = DI1
The function is activated/deactivated through digital input DI1. 1 = activation,
0 = deactivation.
The internal sleep criteria set by parameters
4023
PID SLEEP LEVEL and
4025
WAKE-UP DEV are not effective. The sleep start and stop delay
parameters
4024
PID SLEEP DELAY and
4026
WAKE-UP DELAY are
effective.
2 = DI2
See selection 1 (DI1).
3 = DI3
See selection 1 (DI1).
4 = DI4
See selection 1 (DI1).
5 = DI5
See selection 1 (DI1).
7 = INTERNAL
Activated and deactivated automatically as defined by parameters
4023
PID
SLEEP LEVEL and
4025
WAKE-UP DEV.
-1 = DI1(INV)
The function is activated/deactivated through inverted digital input DI1.
1 = deactivation, 0 = activation.
The internal sleep criteria set by parameters
4023
PID SLEEP LEVEL and
4025
WAKE-UP DEV are not effective. The sleep start and stop delay
parameters
4024
PID SLEEP DELAY and
4026
WAKE-UP DELAY are
effective.
-2 = DI2(INV)
See selection DI1(INV).
-3 = DI3(INV)
See selection DI1(INV).
-4 = DI4(INV)
See selection DI1(INV).
-5 = DI5(INV)
See selection DI1(INV).
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...