129
Fault tracing
CODE
ALARM
CAUSE
WHAT TO DO
A2017
OFF BUTTON
Drive stop command has been
given from control panel when
local control lock is active.
Disable the local control mode lock by
parameter
1606
LOCAL LOCK and retry.
A2018
1)
PID SLEEP
Sleep function has entered the
sleeping mode.
See parameter group
40 PROCESS PID
SET 1
.
A2023
EMERGENCY STOP
Drive has received emergency
stop command and ramps to stop
according to ramp time defined by
parameter
2208
EMERG DEC
TIME.
Check that it is safe to continue operation.
Return emergency stop push button to
normal position.
A2026
INPUT PHASE LOSS
(programmable
fault function,
parameter
3016
SUPPLY PHASE)
Intermediate circuit DC voltage is
oscillating due to missing input
power line phase or blown fuse.
Alarm is generated when DC
voltage ripple exceeds 14% of
nominal DC voltage.
Check input power line fuses.
Check for input power supply imbalance.
Check fault function parameter setting.
1)
Even when the relay output is configured to indicate alarm conditions (for example, parameter
1401
RELAY OUTPUT 1 = 5 [ALARM] or 16 [FLT/ALARM]), this alarm is not indicated by a relay output.
CODE
CAUSE
WHAT TO DO
A5011
Drive is controlled from another source.
Change drive control to the local control mode.
A5012
Direction of rotation is locked.
Enable change of direction. See parameter
1003
DIRECTION.
A5013
Panel control is disabled because start inhibit is active.
Start from the panel is not possible. Reset the
emergency stop command or remove the 3-wire stop
command before starting from the panel.
See section
3-wire macro
on page
72
and parameters
1001
EXT1 COMMANDS,
1002
EXT2 COMMANDS
and
2109
EMERG STOP SEL.
A5014
Panel control is disabled because of drive fault.
Reset drive fault and retry.
A5015
Panel control is disabled because the local control mode
lock is active.
Deactivate the local control mode lock and retry. See
parameter
1606
LOCAL LOCK.
A5019
Writing non-zero parameter value is prohibited.
Only parameter reset is allowed.
A5022
Parameter is write protected.
Parameter value is read-only and cannot be changed.
A5023
Parameter change is not allowed, when drive is running.
Stop drive and change parameter value.
A5024
Drive is executing task.
Wait until task is completed.
A5026
Value is at or below minimum limit.
Contact your local ABB representative.
A5027
Value is at or above maximum limit.
Contact your local ABB representative.
A5028
Invalid value
Contact your local ABB representative.
A5029
Memory is not ready.
Retry.
A5030
Invalid request
Contact your local ABB representative.
A5031
Drive is not ready for operation, for example, due to low
DC voltage.
Check input power supply.
A5032
Parameter error
Contact your local ABB representative.
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...