53
Start-up and control with I/O
• motor nominal frequency (parameter
9907
MOTOR NOM
FREQ)
Set the maximum value for external reference REF1
(parameter
1105
REF1 MAX).
Set constant speeds (drive output frequencies) 1, 2 and 3
(parameters
1202
CONST SPEED 1,
1203
CONST SPEED 2
and
1204
CONST SPEED 3).
Set the minimum value (%) corresponding to the minimum
signal for AI(1) (parameter
1301
MINIMUM AI1).
Set the maximum limit for the drive output frequency
(parameter
2008
MAXIMUM FREQ).
Select the motor stop function (parameter
2102
STOP
FUNCTION).
LOC
9907
s
PAR
FWD
LOC
1105
s
PAR
FWD
LOC
1202
s
PAR
FWD
LOC
1203
s
PAR
FWD
LOC
1204
s
PAR
FWD
LOC
1301
s
PAR
FWD
LOC
2008
s
PAR
FWD
LOC
2102
s
PAR
FWD
DIRECTION OF THE MOTOR ROTATION
Check the direction of the motor rotation.
• Turn the potentiometer fully counterclockwise.
• If the drive is in remote control (REM shown on the left),
switch to local control by pressing
LOC
.
REM
• Press
to start the motor.
• Turn the potentiometer slightly clockwise until the motor
rotates.
• Check that the actual direction of the motor is the same as
indicated on the display (FWD means forward and REV
reverse).
• Press
to stop the motor.
LOC
2102
s
PAR
FWD
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...