Actual signals and parameters
DI1
DI2
Operation
0
0
Stop
1
0
Start forward
0
1
Start reverse
1
1
Stop
Parameters in the Long parameter mode
The following table includes the complete descriptions of all parameters that are
visible only in the Long parameter mode. See section
Parameter modes
on page
65
for how to select the parameter mode.
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
10 START/STOP/DIR
The sources for external start, stop and direction control
1001
EXT1 COMMANDS
Defines the connections and the source for the start, stop and direction
commands for external control location 1 (EXT1).
2 = DI1,2
0 = NOT SEL
No start, stop and direction command source
1 = DI1
Start and stop through digital input DI1. 0 = stop, 1 = start. Direction is fixed
according to parameter
1003
DIRECTION (setting REQUEST = FORWARD).
2 = DI1,2
Start and stop through digital input DI1. 0 = stop, 1 = start. Direction through
digital input DI2. 0 = forward, 1 = reverse. To control direction, parameter
1003
DIRECTION setting must be 3 (REQUEST).
3 = DI1P,2P
Pulse start through digital input DI1. 0 -> 1: Start. (In order to start the drive,
digital input DI2 must be activated prior to the pulse fed to DI1.)
Pulse stop through digital input DI2. 1 -> 0: Stop. Direction of rotation is fixed
according to parameter
1003
DIRECTION (setting REQUEST = FORWARD).
Note:
When the stop input (DI2) is deactivated (no input), the control panel
start and stop keys are disabled.
4 = DI1P,2P,3
Pulse start through digital input DI1. 0 -> 1: Start. (In order to start the drive,
digital input DI2 must be activated prior to the pulse fed to DI1.)
Pulse stop through digital input DI2. 1 -> 0: Stop. Direction through digital
input DI3. 0 = forward, 1 = reverse. To control direction, parameter
1003
DIRECTION setting must be 3 (REQUEST).
Note:
When the stop input (DI2) is deactivated (no input), the control panel
start and stop keys are disabled.
5 = DI1P,2P,3P
Pulse start forward through digital input DI1. 0 -> 1: Start forward. Pulse start
reverse through digital input DI2. 0 -> 1: Start reverse. (In order to start the
drive, digital input DI3 must be activated prior to the pulse fed to DI1/DI2).
Pulse stop through digital input DI3. 1 -> 0: Stop. To control the direction,
parameter
1003
DIRECTION setting must be 3 (REQUEST).
Note:
When the stop input (DI3) is deactivated (no input), the control panel
start and stop keys are disabled.
8 = KEYPAD
Start, stop and direction commands through control panel when EXT1 is
active. To control the direction, parameter
1003
DIRECTION setting must be
3 (REQUEST).
9 = DI1F,2R
Start, stop and direction commands through digital inputs DI1 and DI2.
Parameter
1003
DIRECTION setting must be 3 (REQUEST).
20 = DI5
Start and stop through digital input DI5. 0 = stop, 1 = start. Direction is fixed
according to parameter
1003
DIRECTION (setting REQUEST = FORWARD).
21 = DI5,4
Start and stop through digital input DI5. 0 = stop, 1 = start. Direction through
digital input DI4. 0 = forward, 1 = reverse. To control direction, parameter
1003
DIRECTION setting must be 3 (REQUEST).
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...