Actual signals and parameters
111
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
3015
UNDERLOAD CURVE
Selects the load curve for the underload function. See parameter
3013
UNDERLOAD FUNC.
T
M
= nominal torque of the motor
T
M
ƒ
N
= nominal frequency of the motor (par.
9907
)
(%)
Underload curve types
80
3
70%
60
2
50%
40
1
5
30%
20
4
f
0
ƒ
N
2.4 ·
ƒ
N
1
1
…5
Number of the load curve type in the figure
3016
SUPPLY PHASE
Selects how the drive reacts to supply phase loss, that is when DC voltage
ripple is excessive.
0 = FAULT
0 = FAULT
The drive trips on fault
INPUT PHASE LOSS
(code:
F0022
) and the motor
coasts to stop when the DC voltage ripple exceeds 14% of the nominal DC
voltage.
1 = LIMIT/ALARM
Drive output current is limited and alarm
INPUT PHASE LOSS
(code:
A2026
)
is generated when the DC voltage ripple exceeds 14% of the nominal DC
voltage.
There is a 10 s delay between the activation of the alarm and the output
current limitation. The current is limited until the ripple drops under the
minimum limit, 0.3 ·
I
hd
.
2 = ALARM
The drive generates alarm
INPUT PHASE LOSS
(code:
A2026
) when the DC
ripple exceeds 14% of the nominal DC voltage.
3017
EARTH FAULT
Selects how the drive reacts when an earth (ground) fault is detected in the
motor or the motor cable. The protection is active only during start. An earth
fault in the input power line does not activate the protection
Note:
Disabling earth (ground) fault may void the warranty.
1 = ENABLE
0 = DISABLE
No action
1 = ENABLE
The drive trips on fault
EARTH FAULT
(code:
F0016
).
3021
AI1 FAULT LIMIT
Defines the fault or alarm level for analog input AI1. If parameter
3001
AI<MIN FUNCTION is set to 1 (FAULT), 2 (CONST SP 7) or 3 (LAST
SPEED), the drive generates alarm or fault
AI1 LOSS
(code:
A2006
or
F0007
), when the analog input signal falls below the set level.
Do not set this limit below the level defined by parameter
1301
MINIMUM
AI1.
0.0%
0.0
…100.0%
Value in percent of the full signal range
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...