55
Start-up and control with I/O
How to control the drive through the I/O interface
The table below instructs how to operate the drive through the digital and analog
inputs when:
• the motor start-up is performed, and
• the default (standard) parameter settings are valid.
PRELIMINARY SETTINGS
If you need to change the direction of rotation, check that parameter
1003
DIRECTION is set to 3 (REQUEST).
Ensure that the control connections are wired according to the
connection diagram given for the ABB standard macro.
Ensure that the drive is in remote control. Press key
LOC
to switch
REM
between remote and local control.
See
Default I/O connection
diagram
on page
46
.
In remote control, the panel
display shows text REM.
STARTING AND CONTROLLING THE SPEED OF THE MOTOR
Start by switching digital input DI1 on.
Text FWD starts flashing fast and stops after the setpoint is reached.
Regulate the drive output frequency (motor speed) by adjusting the
voltage or current of the analog input AI(1).
REM
0
.
0
Hz
OUTPUT
FWD
REM
50
.
0
Hz
OUTPUT
FWD
CHANGING THE DIRECTION OF THE MOTOR ROTATION
Reverse direction: Switch digital input DI2 on.
Forward direction: Switch digital input DI2 off.
REM
50
.
0
Hz
OUTPUT
REV
REM
50
.
0
Hz
OUTPUT
FWD
STOPPING THE MOTOR
Switch digital input DI1 off.
The motor stops and text FWD starts flashing slowly.
REM
0
.
0
Hz
OUTPUT
FWD
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...