Actual signals and parameters
110
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
3010
STALL FUNCTION
Selects how the drive reacts to a motor stall condition. The protection wakes
up if the drive has operated in a stall region (see the figure below) longer than
the time set by parameter
3012
STALL TIME.
Current
(A)
Stall region
0.95 · par 2003 MAX CURRENT
f
Par. 3011
0 = NOT SEL
0 = NOT SEL
Protection is inactive.
1 = FAULT
The drive trips on fault
MOTOR STALL
(code:
F0012
) and the motor coasts
to stop.
2 = ALARM
The drive generates alarm
MOTOR STALL
(code:
A2012
).
3011
STALL FREQUENCY
Defines the frequency limit for the stall function. See parameter
3010
STALL
FUNCTION.
20.0 Hz
0.5
…50.0 Hz
Frequency
3012
STALL TIME
Defines the time for the stall function. See parameter
3010
STALL
FUNCTION.
20 s
10
…400 s
Time
3013
UNDERLOAD FUNC
Selects how the drive reacts to underload. The protection wakes up if
- the motor torque falls below the curve selected by parameter
3015
UNDERLOAD CURVE,
- output frequency is higher than 10% of the nominal motor frequency and
- the above conditions have been valid longer than the time set by parameter
3014
UNDERLOAD TIME.
0 = NOT SEL
0 = NOT SEL
Protection is inactive.
1 = FAULT
The drive trips on fault
UNDERLOAD
(code:
F0017
) and the motor coasts to
stop.
2 = ALARM
The drive generates alarm
UNDERLOAD
(code:
A2011
).
3014
UNDERLOAD TIME
Defines the time limit for the underload function. See parameter
3013
UNDERLOAD FUNC.
20 s
1
0…400 s
Time limit
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...