Actual signals and parameters
107
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
30 FAULT FUNCTIONS
Programmable protection functions
3001
AI<MIN FUNCTION
Defines the drive response if the analog input (AI) signal drops below the
fault limits and AI is used
• as the active reference source (group
11 REFERENCE SELECT
)
• as the process or external PID controllers' feedback or setpoint source
(group
40 PROCESS PID SET 1
) and the corresponding PID controller is
active.
3021
AI1 FAULT LIMIT sets the fault limits
0 = NOT SEL
0 = NOT SEL
Protection is inactive.
1 = FAULT
The drive trips on fault
AI1 LOSS
(code:
F0007
) and the motor coasts to stop.
Fault limit is defined by parameter
3021
AI1 FAULT LIMIT.
2 = CONST SP 7
The drive generates alarm
AI1 LOSS
(code:
A2006
) and sets the speed to
the value defined by parameter
1208
CONST SPEED 7. The alarm limit is
defined by parameter
3021
AI1 FAULT LIMIT.
WARNING!
Make sure that it is safe to continue operation in case
the analog input signal is lost.
3 = LAST SPEED
The drive generates alarm
AI1 LOSS
(code:
A2006
) and freezes the speed to
the level the drive was operating at. The speed is determined by the average
speed over the previous 10 seconds. The alarm limit is defined by parameter
3021
AI1 FAULT LIMIT.
WARNING!
Make sure that it is safe to continue operation in case
the analog input signal is lost.
3003
EXTERNAL FAULT 1
Selects an interface for an external fault 1 signal.
0 = NOT SEL
0 = NOT SEL
Not selected
1 = DI1
External fault indication through digital input DI1. 1: Fault trip on
EXT FAULT
1
(code:
F0014
). Motor coasts to stop. 0: No external fault.
2 = DI2
See selection DI1.
3 = DI3
See selection DI1.
4 = DI4
See selection DI1.
5 = DI5
See selection DI1.
-1 = DI1(INV)
External fault indication through inverted digital input DI1. 0: Fault trip on
EXT
FAULT 1
(code:
F0014
). Motor coasts to stop. 1: No external fault.
-2 = DI2(INV)
See selection DI1(INV).
-3 = DI3(INV)
See selection DI1(INV).
-4 = DI4(INV)
See selection DI1(INV).
-5 = DI5(INV)
See selection DI1(INV).
3004
EXTERNAL FAULT 2
Selects an interface for an external fault 2 signal.
0 = NOT SEL
See parameter
3003
EXTERNAL FAULT 1.
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...