Actual signals and parameters
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
13 ANALOG INPUTS
Analog input signal processing
1301
MINIMUM AI1
Defines the minimum %-value that corresponds to minimum mA/(V) signal for
analog input AI1. When used as a reference, the value corresponds to the
reference minimum setting.
0...20 mA = 0...100%
4...20 mA = 20...100%
Example: If AI1 is selected as the source for external reference REF1, this
value corresponds to the value of parameter
1104
REF1 MIN.
Note:
MINIMUM AI value must not exceed MAXIMUM AI value.
0.0%
0.0
…100.0%
Value in percent of the full signal range. Example: If the minimum value for
analog input is 4 mA, the percent value for
0…20 mA range is:
(4 mA / 20 mA) · 100% = 20%
1302
MAXIMUM AI1
Defines the maximum %-value that corresponds to maximum mA/(V) signal
for analog input AI1. When used as a reference, the value corresponds to the
reference maximum setting.
0...20 mA = 0...100%
4...20 mA = 20...100%
Example: If AI1 is selected as the source for external reference REF1, this
value corresponds to the value of parameter
1105
REF1 MAX.
100.0%
0.0
…100.0%
Value in percent of the full signal range. Example: If the maximum value for
analog input is 10 mA, the percent value for
0…20 mA range is:
(10 mA / 20 mA) · 100% = 50%
1303
FILTER AI1
Defines the filter time constant for analog input AI1, that is the time within
which 63% of a step change is reached.
%
Unfiltered signal
100
63
Filtered signal
t
Time constant
0.1 s
0.0
…10.0 s
Filter time constant
14 RELAY OUTPUTS
Status information indicated through relay output and relay operating delays
1401
RELAY OUTPUT 1
Selects a drive status indicated through relay output RO. The relay energizes
when the status meets the setting.
3 =
FAULT(-1)
0 = NOT SEL
Not used
1 = READY
Ready to function: Run enable signal on, no fault, supply voltage within
acceptable range and emergency stop signal off.
2 = RUN
Running: Start signal on, Run enable signal on, no active fault.
3 = FAULT(-1)
Inverted fault. Relay is de-energized on a fault trip.
4 = FAULT
Fault
5 = ALARM
Alarm
6 = REVERSED
Motor rotates in reverse direction.
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...