90
Actual signals and parameters
Parameters in the Long parameter mode
Index
Name/Selection
Description
Def
3 = AI1/JOYST
Analog input AI1 as joystick. The minimum input signal runs the motor at the
maximum reference in the reverse direction, the maximum input at the
maximum reference in the forward direction. Minimum and maximum
references are defined by parameters
1104
REF1 MIN and
1105
REF1 MAX.
Note:
Parameter
1003
DIRECTION must be set to 3 (REQUEST).
Speed ref.
par. 1301 = 20%, par 1302 = 100%
(REF1)
1105
1104
1104
-2%
+2%
0
AI1
- 1104
-
1104
-
1105
Hysteresis 4%
of full scale
2 V / 4 mA
6
10 V / 20 mA
WARNING!
If parameter
1301
MINIMUM AI1 is set to 0 V and analog input
signal is lost (that is 0 V), the rotation of the motor is reversed to the
maximum reference. Set the following parameters to activate a fault when
analog input signal is lost:
Set parameter
1301
MINIMUM AI1 to 20% (2 V or 4 mA).
Set parameter
3021
AI1 FAULT LIMIT to 5% or higher.
Set parameter
3001
AI<MIN FUNCTION to 1 (FAULT).
5 = DI3U,4D(R)
Digital input DI3: Reference increase. Digital input DI4: Reference decrease.
Stop command resets the reference to zero. Parameter
2205
ACCELER
TIME 2 defines the rate of the reference change.
6 = DI3U,4D
Digital input DI3: Reference increase. Digital input DI4: Reference decrease.
The program stores the active speed reference (not reset by a stop
command). When the drive is restarted, the motor ramps up with the selected
acceleration rate to the stored reference. Parameter
2205
ACCELER TIME2
defines the rate of the reference change.
11 = DI3U,4D(RNC)
Digital input DI3: Reference increase. Digital input DI4: Reference decrease.
Stop command resets the reference to zero. The reference is not saved if the
control source is changed (from EXT1 to EXT2, from EXT2 to EXT1 or from
LOC to REM). Parameter
2205
ACCELER TIME 2 defines the rate of the
reference change.
12 = DI3U,4D(NC)
Digital input DI3: Reference increase. Digital input DI4: Reference decrease.
The program stores the active speed reference (not reset by a stop
command). The reference is not saved if the control source is changed (from
EXT1 to EXT2, from EXT2 to EXT1 or from LOC to REM). When the drive is
restarted, the motor ramps up with the selected acceleration rate to the
stored reference. Parameter
2205
ACCELER TIME 2 defines the rate of the
reference change.
14 = AI1+POT
Reference is calculated with the following equation:
REF = AI1(%) + POT(%) - 50%
16 = AI1-POT
Reference is calculated with the following equation:
REF = AI1(%) + 50% - POT(%)
30 = DI4U,5D
See selection DI3U,4D.
31 = DI4U,5D(NC)
See selection DI3U,4D(NC).
32 = FREQ INPUT
Frequency input
Содержание ACS150 series
Страница 4: ......
Страница 5: ......
Страница 15: ...14 Safety ...
Страница 19: ...18 Introduction to the manual ...
Страница 39: ...38 Planning the electrical installation ...
Страница 51: ...50 Installation checklist ...
Страница 57: ...56 Start up and control with I O ...
Страница 69: ...68 Control panel ...
Страница 79: ...78 Application macros ...
Страница 160: ...L Q M 0 I II D I II I I ro I m D en m D D Q Q f 3AFE68633931 A 0 Frame size R2 IP20 INEMA 1 ...
Страница 161: ...ji 4 I 5 I 6 4 J ...
Страница 162: ......
Страница 163: ...160 Dimension drawings ...
Страница 169: ...166 Appendix Process PID control ...
Страница 171: ...168 ...