background image

 

 

 

USER MANUAL 

Mobeye

®

 WaterGuard  

CM2300 

 

 

SW version 5.n

 

Содержание WaterGuard CM2300

Страница 1: ...USER MANUAL Mobeye WaterGuard CM2300 SW version 5 n ...

Страница 2: ...device from moisture heat and water splashing Not intended for external use The guidelines for the battery usage must be regarded Do not expose the device to strong vibrations Do not let it fall from height Do not use in an environment where any inflammable gases vapors or dust are present or could be present Repair of the device may only be carried out by people trained for Mobeye repair If the d...

Страница 3: ...ard 10 4 3 Enter the program mode 11 4 4 Activate the device in the portal 11 4 5 Configuration and synchronisation 12 4 6 Basics of the Mobeye Internet Portal 12 4 7 Switching on off 14 4 8 Confirmation of the alarm message 14 4 9 System reset 15 5 Possible settings 16 5 1 Alarm phone numbers 16 5 2 Call on off 16 5 3 SMS on off 16 5 4 Alarm delay time 17 5 5 Alarm repeat time 17 5 6 Input type 1...

Страница 4: ...programming with own SIM 22 7 1 List of SMS commands 22 7 2 Switching on off 23 7 3 Confirmation of the alarm message 24 7 4 System reset 24 7 5 SMS reports when using own SIM card 25 7 6 Technical messages 26 8 Status feedback 27 ...

Страница 5: ... Mobeye Internet Portal In this management environment the device is given additional functions such as online programming status and history display more options for forwarding messages and it will monitor test messages keep alive In addition the Mobeye SIM is a cost effective M2M roaming SIM card that can use multiple providers per country worldwide and offers more security than a provider bound...

Страница 6: ... alarm as text message and or e mail to the alarm contacts When one of the inputs remain in the alarm status the Mobeye WaterGuard repeats sending the alarm message via the Mobeye Internet Portal every four hours When an external power supply is used and a power failure occurs the Mobeye WaterGuard sends a power failure message to Mobeye Internet Portal to be forwarded to the alarm contacts When t...

Страница 7: ...Mobeye Water alarm As soon as the water detection has ended an SMS text message is sent to the set telephone numbers containing the text Mobeye Water Level OK When one of the additional inputs is activated by a sensor the WaterGuard sends an alarm SMS text message and calls the phone numbers programmed in by the user When one of the inputs remain in the alarm status the WaterGuard repeats sending ...

Страница 8: ...the device in the Mobeye Internet Portal e Program the options and synchronise 7 Programming when using your own SIM card a Enter the program mode b Program the settings Steps 1 to 5 are described in sections 3 1 up to 3 5 Step 6 is described in chapter 4 Step 7 can be found in chapter 6 3 1 INSERT THE SIM CARD Open the enclosure by removing the 4 screws and insert the SIM card into the module Pus...

Страница 9: ...l not be deleted since they are stored in the device memory 3 3 CONNECT THE WATER SENSOR Plug the external water sensor into the socket and press it firmly Mount the sensor to a fixed place in vertical position at the height where the presence of water should be detected If necessary use a metal strip for attaching the sensor In case the sensor should detect the absence of water the input type nee...

Страница 10: ...riggered input will lead to alarm notifications Insert the 2 wires of the external sensor through the hole in the enclosure and insert them in the two connectors of input 1 press on the green pins for connecting the wires It does not matter which wire is connected to which connector As default the inputs are programmed as Normally Open NO contacts This means the inputs are triggered if the input i...

Страница 11: ...ernet Portal choose activate SIM card on the Add Device screen Fill in the SIM card number This is the number written on the plastic SIM card below the barcode You can take the entire number or only the last 8 digits The screen leads you through several pop ups If asked choose the device type search for CM2300 and select the type of contract CM2300 SIM Portal Monitoring At the moment you accept th...

Страница 12: ... 3 minutes the GSM module remains active ready to be activated in the portal In a battery operated unit a time out occurs after 3 minutes and the GSM module switches off in order to save the batteries In this low power mode the LED flashes once per 3 seconds 4 4 ACTIVATE THE DEVICE IN THE PORTAL If the LED on the outside flashes once per second you activate the device in the Mobeye Internet Portal...

Страница 13: ...until it connects to the network 4 6 BASICS OF THE MOBEYE INTERNET PORTAL Dashboard With multiple devices the dashboard shows all devices with the alarm messages in the last 24 hours missed test messages and low battery status Select a device to go to the details of a specific device Status History The status block shows values that provide information about the status of the unit If the Synchroni...

Страница 14: ...ages you link the contact persons who receive alarm and service messages via text message and or e mail Service messages can be warnings about missed test messages and low battery voltage To add a contact person first create it as a contact This can be done via the or in the main menu under the blue Contacts tab in the block Alarm calls from device the max 5 alarm numbers that are called directly ...

Страница 15: ...1 second The green LED blinks once every 3 seconds battery powered or stays on continuously in case of an external power supply If powered externally GSM is open switching can be done via SMS commands SMS command to switch on CODE ARM SMS command to switch off CODE DISARM example 1111 ARM The status can be requested via SMS command CODE STATUS 4 8 CONFIRMATION OF THE ALARM MESSAGE When the system ...

Страница 16: ...settings 1 Remove the batteries and external power supply 2 Press the outside button while reinserting the batteries Keep it pressed for about another 5 seconds 3 Release the button immediately after the LED starts to flash 4 If relevant connect the external power supply After a successful reset the status LED will blink green to indicate that the module is not configured The security code is back...

Страница 17: ...r telephone calls and or text messages from the unit This is not mandatory when using the Mobeye Internet Portal If no telephone numbers have been entered the notifications will only be sent to the portal and forwarded by SMS and or e mail from there Note the unlimited number of contacts who receive SMS e mail may be different from the numbers programmed on TEL1 TEL5 5 2 CALL ON OFF Even if the al...

Страница 18: ...ime is set to 4 hours 5 6 INPUT TYPE The input type defines the character of the water sensor input input IN1 and IN2 This can be Normally Open NO or Normally Closed NC If an input is set to NO the alarm will be triggered as soon as the terminals of the input are closed If the input is set to NC the alarm is triggered when the connection between the input terminals is broken The default input type...

Страница 19: ... failure and the alarm notification If the power is restored within the delay time no alarm is sent The time can be set between 0 and 999 minutes As default the delay time is set to 0 5 10 BUTTONLOCK It can be useful to lock the on off button to prevent the unit from being switched off unintentionally As default the buttonlock is unlocked so the button is enabled To disable the button the buttonlo...

Страница 20: ...ised after the test message setting a specific time of the test message can help the process of remote programming Example if you force a daily test message at 17 30 hrs you can prepare new settings and be sure they are loaded into the device before the evening The interval between the test messages can be set between 0 days no test message and 30 days The default test interval is set to 7 weekly ...

Страница 21: ...rmally takes 10 30 seconds As soon as the network has been established and the program mode has been reached the LED flashes 1 sec on 1 sec off or stays on continuously in case the unit has been configured yet During 3 minutes the GSM module remains active ready to receive SMS commands In a battery operated unit a time out occurs if no correct command is received for 3 minutes the GSM module switc...

Страница 22: ...n SMS text message with the security code and the command 3 The green LED blinks 3 times to indicate the successful configuration In case of an incorrect command the red LED flashes 5 times SMS messages have the following content CODE COMMAND OPTION Example 1111 TEL1 44772345678 CODE stands for the security code factory setting is 1111 Do not forget the space character between security code and co...

Страница 23: ... off CALL ON OFF ON SMS on off SMS ON OFF ON Input type input 1 TYPEIN1 NO NC NO Input type input 2 TYPEIN2 NO NC NO Input type water sensor TYPEIN3 NO NC NO Delay on input 1 DELAY1 0 999 sec 1 Delay on input 2 DELAY2 0 999 sec 1 Delay on water sensor DELAY3 0 999 sec 30 Inactive time input 1 INACTIVEIN1 0 60 min 0 Inactive time input 2 INACTIVEIN2 0 60 min 0 Inactive time water sensor INACTIVEIN3...

Страница 24: ...ys 0 Time test message TESTTIME hhmm Examples Set phone number 1 1111 TEL1 0712345678 Delete phone number 1 1111 del1 Be aware of the space between 1111 and the command 7 2 SWITCHING ON OFF After the previous steps the Mobeye WaterGuard is ready for use It is armed switched on automatically In order to switch off disarm the Mobeye WaterGuard Press the on off button at the upper side for 1 second T...

Страница 25: ...ll When you pick up the phone you will hear beeps It is possible to acknowledge the phone call by answering the phone and pressing any key The other alarm numbers will not be called afterwards This works for most telephones By switching off the SMS function the system will only call This prevents the other numbers being notified by SMS 7 4 SYSTEM RESET To reset the Mobeye WaterGuard to its factory...

Страница 26: ...MS command status request STATUS example 1111 STATUS LIST OF SETTINGS The settings can be requested by sending following SMS text message SMS command list basic settings SET SMS command list advanced settings SETA SMS command list of texts TEXT example 1111 SET LIST OF PHONE NUMBERS The list of telephone numbers can be requested by sending following SMS text message SMS command list of phone numbe...

Страница 27: ...ternal power is restored or the adapter is plugged in a socket batteries do not need to be replaced delayed message If delayed message is added to the SMS text messages the message couldn t be sent earlier due to a SIM card failure or GSM network failure Batteries too low Module shutting down The module has shut down due to low voltage Replace the batteries or connect the power supply to restart t...

Страница 28: ...the network connection is established 2 flashes red every 3 seconds No GSM connection Try the SIM card in any mobile telephone replace SIM card using other telecom provider try the module at another location 3 flashes red every 3 seconds No valid SIM card or wrong PIN Try the SIM card in any mobile telephone remove PIN code check credit replace SIM card Blinking 3 times green Successful programmin...

Страница 29: ...ax ca 500 mA Power consumption 12V ca 50 mA stand by max ca 500 mA Dimensions 80 x 60 x 40 mm Ambient temperature 10 C until 50 C This manual is published by Mobeye All rights the translation included are reserved Any reproduction either photocopy microfilm or saved in an automated data dictionary only after written approval of the Publisher Reprinting even in summary is prohibited This user manua...

Страница 30: ...29 ...

Страница 31: ...30 ...

Страница 32: ......