Alarm List-251
110
The universal three clock
process executing sequence
error process was executed
according to unexpected
timing.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
EAXA21 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the EAXA21 board. Save the
CMOS.BIN before replace the board to be safe.
112
The sequence was untimely
executed in the
segment_OPT1 process
although it was not the
execution timing.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
EAXA21 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the EAXA21 board. Save the
CMOS.BIN before replace the board to be safe.
113
The sequence was untimely
executed in the
segment_OPT2 process
although it was not the
execution timing.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
EAXA21 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the EAXA21 board. Save the
CMOS.BIN before replace the board to be safe.
120
A general-purpose 10ms
process did not complete
within the time set on the
scheduling table.
Software operation error
occurred
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, save the CMOS.BIN in maintenance
mode, and then contact your Yaskawa representative about
occurrence status (operating procedure).
EAXA21 board failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, replace the EAXA21 board. Save the
CMOS.BIN before replace the board to be safe.
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy