Alarm List-893
YFC22 board failure
(1)Reset the alarm.
(2)If the alarm occurs again, replace the YFC22 board.
In a system where a plurality of YFC22 boards are connected, replace
the board, which is connected to the GSIN signal on which the alarm
occurred.
YSF22 board failure
(1)Reset the alarm.
(2)If the alarm occurs again, replace the YSF22 board.
In a system where a plurality of YSF22 boards are connected, replace
the board on which the alarm occurred.
Other
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
4772
YSF24 GENERAL
OUTPUT DIAG.
ERROR
The meaning of each sub
code is as follows:
CPU1 1:XOUT1
CPU1 2:XOUT2
CPU1 3:XOUT3
CPU1 4:XOUT4
CPU1 5:XOUT5
CPU1 6:XOUT6
CPU1 7:XOUT7
CPU1 8:XOUT8
CPU2 1:XOUT1
CPU2 2:XOUT2
CPU2 3:XOUT3
CPU2 4:XOUT4
CPU2 5:XOUT5
CPU2 6:XOUT6
CPU2 7:XOUT7
CPU2 8:XOUT8
Connection failure
(1)Reset the alarm.
(2)If the alarm occurs again, check the connection and inserting state
of the following cables and connectors.
∙
YFC24
∙
Cable continuity between YSF22 board and YFC24 board.
YSF21 board failure
(1)Reset the alarm.
(2)If the alarm occurs again, replace the YSF21 board.
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy