Alarm List-157
12
An error was found in the
specified number of registers
which are used by the system
data "CURR.POS. (PULSE)"
of allocation configuration.
Setting error
(1)Check the following settings.
∙
Allocation configuration for the TOYOPUC
Connection failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, check the connection and insertion of the
following connector.
∙
The PCI connector of the TOYOPUC board
other
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
14
An error was found in the
specified number of registers
which are used by the system
data "CURR.POS. (XYZ)" of
allocation configuration.
Setting error
(1)Check the following settings.
∙
Allocation configuration for the TOYOPUC
Connection failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, check the connection and insertion of the
following connector.
∙
The PCI connector of the TOYOPUC board
other
If the alarm occurs again, save the CMOS.BIN in maintenance mode,
and then contact your Yaskawa representative about occurrence
status (operating procedure).
16
An error was found in the
specified number of registers
which are used by the system
data "WELDING INFO." of
allocation configuration.
Setting error
(1)Check the following settings.
∙
Allocation configuration for the TOYOPUC
Connection failure
(1)Turn the power OFF then back ON.
(2)If the alarm occurs again, check the connection and insertion of the
following connector.
∙
The PCI connector of the TOYOPUC board
Alarm
Number
Alarm Name
Sub
Code
Meaning
Cause
Remedy