Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
■
SP low limit/high limit
The SP low limit and high limit can be set to limit the SP range.
• If the setting is made so that the SP low limit is greater than the SP high limit, the
operation is performed with the low limit swapped for the high limit
automatically.
Handling Precautions
When [C01: PV input range type] is set, the SP low limit and high limit
are initialized.
■
DI Assignment of SP ramp enabled/disabled
The SP ramp enabled/disabled can be set for the internal contact function using the
DI assignment.
• Details of SP ramp enabled/disabled with internal contact function
The following shows the SP ramp enabled/disabled setting with the internal
contact ON/OFF:
OFF: SP ramp enabled.
ON: SP ramp disabled.
The SP ramp enabled/disabled is set for only one internal contact.
• When the SP ramp is set disabled, the SP ramp operation is stopped and the SP
value becomes the final SP.
Item (Bank)
Display
Contents
Initial value