6-13
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
Display
Item
Contents
Initial
value
User
level
Remarks
Output operation at
changing Auto/Manual
0: Bumpless transfer
1: Preset
0
1
Displayed when the control
method is other than the
ON/OFF control (CtrL
≠
0).
When the operation mode is
the MANUAL mode at power
ON, the preset MANUAL
value (C20) becomes the
Manipulated Variable (MV).
Preset MANUAL
value
-10.0 to +110.0%
(Used when the operation mode is
the MANUAL mode at power ON.)
0.0 or
50.0
1
Initial output type
(mode) of PID control
0: Auto
1: Not initialized.
2: Initialized (If SP value different
from the current value is input.)
0
2
Initial output of PID
control
-10.0 to +110.0%
0.0 or
50.0
2
Heat/Cool control
0: Not used.
1: Used.
0
0
Displayed when the control
output type is other than R1
(motor drive relay output),
and when the control method
is other than the ON/OFF
control (CtrL
≠
0).
When set at “1”, the control
action is set to the reverse
action (C14 = 0), the preset
MANUAL value (C20) is set
to “50.0”, and the initial
output of the PID control
(C22) is changed to “50.0”.
Heat/Cool selection
0: Normal
1: Energy saving
0
1
Heat/Cool control
dead zone
-100.0 to +100.0%
0.0
0
Heat/Cool control
change point
-10.0 to +110.0%
50.0
2
LSP system group
1 to 8
1
0
SP ramp unit
0: 0.1U/s
1: 0.1U/min
2: 0.1U/h
1
2
"0.1U" shows that the decimal
point position of the PV is
shifted one digit rightward.
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......