6-27
Chapter 6. LIST OF DISPLAYS AND SETTING DATA
Display
Item
Contents
Initial
value
User
level
Remarks
Control output 2
Operation type
Same as Control output 1 Operation
type.
0: Default output
1: MV1
2: MV2
3 to 6: Function 1 to 4
0
2
Displayed when the control
output of the model is set to
the position proportional
output or the control output 2
of the model is voltage pulse
output.
When using control output 2,
the default output is MV2.
Control output 2
Output assignment A
Same as Control output 1 Output
assignment A to D.
15
2
Displayed when control
output 2 of the model is set
to the voltage pulse output
and the operation type of
control output 2 is set 1 to 4
(ot2.1 > 2).
Control output 2
Output assignment B
0
2
Control output 2
Output assignment C
0
2
Control output 2
Output assignment D
0
2
Control output 2
Polarity A to D
1st digit: Polarity A
2nd digit: Polarity B
3rd digit: Polarity C
4th digit: Polarity D
Same as Control output 1 Polarity A
to D.
The following setting applies to each
digit:
0: Direct
1: Reverse
0000
2
Control output 2
Polarity
0: Direct
1: Reverse
0
2
Control output 2
Latch
0: None
1: Latch (Latch at ON)
2: Latch (Latch at OFF except for
initialization at power ON)
0
2
Event output 1
Operation type
Same as Control output 1 Operation
type.
0: Default output
1: MV1
2: MV2
3 to 6: Function 1 to 4
0
2
Event output 1
Output assignment A
Same as Control output 1 Output
assignment A to D.
2
2
Event output 1
Output assignment B
0
2
Event output 1
Output assignment C
0
2
Event output 1
Output assignment D
0
2
Event output 1
Polarity A to D
1st digit: Polarity A
2nd digit: Polarity B
3rd digit: Polarity C
4th digit: Polarity D
0000
2
Event output 1
Polarity
0: Direct
1: Reverse
0
2
Event output 1
Latch
0: None
1: Latch (Latch at ON)
2: Latch (Latch at OFF except for
initialization at power ON)
0
2
Displayed when the optional
model has Event output 1.
When using Event output 1,
the default output is Internal
Event 1.
Displayed when the optional
model has Event output 1
and the operation type of
Event output 1 is set 1 to 4
(Ev1.1 > 2).
Same as Control output 1 Polarity A
to D.
The following setting applies to each
digit:
0: Direct
1: Reverse
(Continue on next page.)
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......