5-65
■
Alarm OR, special OFF setup, and delay time unit
Alarm OR, special OFF setup, and delay time unit accompanying with the
operation type can be set.
• When the internal event configuration 1 operation type is set at [0: No event], the
internal event configuration 3 (alarm OR, special OFF setup, and delay time unit)
is not displayed.
The following shows the relationship among alarm OR setting, alarm occurred/not
occurred, and internal event ON/OFF:
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Item (Bank)
Display
Contents
Initial value
User level
Internal Event 1
Configuration 3
(Event Configuration bank)
The digits are called 1st digit, 2nd digit, 3rd
digit, and 4th digit from the right end.
1st digit: Alarm OR setup
0:
None
1:
Alarm OR operation
2:
Alarm AND operation
3:
Alarm r OR operation
4:
Alarm r AND operation
2nd digit: Special OFF setup
0:
As usual.
1:
When EV main setting is “0”, the
event is set to “OFF”.
3rd digit: Delay time unit setup
0:
0.1s
1:
1s
2:
1min.
4th digit: Undefined.
0:
Undefined.
0000
High function
0000
Internal Event 2
Configuration 3
(Event Configuration bank)
0000
Internal Event 3
Configuration 3
(Event Configuration bank)
0000
Internal Event 4
Configuration 3
(Event Configuration bank)
0000
Internal Event 5
Configuration 3
(Event Configuration bank)
None
Not occurred
OFF
OFF
Not occurred
ON
ON
Occurred.
OFF
OFF
Occurred.
ON
ON
Alarm
Not occurred
OFF
OFF
OR operation
Not occurred
ON
ON
Occurred.
OFF
ON
Occurred.
ON
ON
Alarm
Not occurred
OFF
OFF
AND operation
Not occurred
ON
OFF
Occurred.
OFF
OFF
Occurred.
ON
ON
Alarm r
Not occurred
OFF
ON
OR operation
Not occurred
ON
ON
Occurred.
OFF
OFF
Occurred.
ON
ON
Alarm r
Not occurred
OFF
OFF
AND operation
Not occurred
ON
ON
Occurred.
OFF
OFF
Occurred.
ON
OFF
Alarm OR setting
Alarm (AL01 to
99) occurred/not
occurred
Internal event
ON/OFF status before
alarm OR process
Internal event
ON/OFF status after
alarm OR process
0000
Internal Event 6
Configuration 3
(Event Configuration bank)
0000
Internal Event 7
Configuration 3
(Event Configuration bank)
0000
Internal Event 8
Configuration 3
(Event Configuration bank)
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......