5-59
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Operation type
Set value
Direct action
Reverse action
of operation
type
Loop diagnosis 1
20
Sub-setting
Main setting
Time
Conditions 3
ON delay
set time
ON delay is started when conditions 1 and 2 are satisfied.
Area satisfying
conditions 1
Area satisfying
conditions 2
Time
Time
PV
MV
EV
ON
HYS
Sub-setting
Main setting
Time
Conditions 3
ON delay
set time
ON delay is started when conditions 1 and 2 are satisfied.
Area satisfying conditions 1
Area satisfying
conditions 2
Time
Time
PV
MV
EV
ON
HYS
The event is turned ON when any change in PV corresponding to increase/decrease in
Manipulated variable (MV) is not observed.
This event is used to detect any fault at the operation end.
●
Setting items
• Main setting: Manipulated variable (MV)
• Sub-setting: PV
• ON delay time: Diagnosis time
●
Operation specifications
The event is turned ON when the value does not reach the PV set in the sub-setting within
the diagnosis time (ON delay time) (conditions 1) even though the MV exceeding the main
setting is held (conditions 2).
●
CAUTION
When setting the ON delay, it is necessary to put in "High function configuration".
The default setting of the ON delay before shipment is 0.0s.
Heat control
Cool control
*1
If the setting is made so that the main setting is greater than the sub setting, the operation is performed with the
main setting swapped for the sub setting automatically.
*2
: When the event type is CT1/2 heater burnout/over-current or CT1/2 heater short-circuit, the status becomes that
the event judgment cannot be made from the time of power ON until that CT input current value is measured
for the first time. In this case, the internal event output is OFF for both of direct action and reverse action in the
direct/reverse setting. To avoid that the output becomes OFF at power ON when used in reverse action, set as
follows:
(Setting example)
For direct/reverse setting of CT1/2 heater burnout/over-current or CT1/2 short-circuit event, select the direct
action, and set the reverse operation in DO assignment calculation of the event output terminal (event terminal
or control output terminal).
CT event(direct action)
[Reverse]
(DO output)
Normally open(0)
Normally open(0)
Normally open(0)
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......