![Yamatake SDC35 User Manual Download Page 228](http://html.mh-extra.com/html/yamatake/sdc35/sdc35_user-manual_905228228.webp)
●
Response Message
A response message corresponding to the command content is returned when the
message is correctly received.
The figure below shows the structure of the response message when the data is
written.
MODBUS ASCII
(1) Start of message
(2) Station address
(3) Write command 10H
(4) Start data address
(5) Number of write data
(6) Checksum
(7) Delimiter
MODBUS RTU
(1) Station address
(2) Write command 10H
(3) Start data address
(4) Number of write data
(5) Checksum
Note
The response message at the time of abnormal termination is the same as that for
the read command.
8-10
Chapter 8. MODBUS COMMUNICATION FUNCTION
(2)
(1)
(3)
(4)
(5)
(6)
(7)
3AH
:
30H
0
31H
1
31H
1
30H
0
30H
0
35H
5
44H
D
44H
D
30H
0
30H
0
30H
0
32H
2
30H
0
42H
B
0DH
CR
0AH
LF
(2)
(1)
(3)
(4)
01H 10H 05H DDH 00H 02H D1H
(5)
3EH
Summary of Contents for SDC35