5-80
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
●
Example 2 The operation is started by the external switch, and then it is stopped
automatically 30min after the temperature has reached the set value.
◆
Explanation
The timer start-up conditions are set to logical AND of DI1 and PV status EVs.
The ON delay timer setting decides the time period after which the operation is
stopped automatically when the temperature has reached the set value.
The mode (RUN/READY) is changed based on a combination of DI1 and timer
ON-OFF.
◆
Setting example
• Event
Note. The internal event No. is indicated at the mark of "x" shown in the display
column.
Set value
Time
30min
Control ON
Control OFF
Temperature
Status
Control OFF
Timer counting after
Operation stop by
status
starting of operation
time-up
DI1
OFF
ON
ON
Timer (Internal EV2)
OFF
OFF
ON
Status of Internal
ON
OFF
ON
Contact 2
Mode
READY
RUN
READY
Event
Display
Internal Event 1
Internal Event 2
Operation type
Ex.C1
32: Timer
4: Deviation high limit
Direct/reverse
Ex.C2
----
0: Direct
Standby
Ex.C2
----
0: No standby
EVENT state at READY
Ex.C2
0: EVENT state at READY
0: EVENT state at READY
is continued.
is continued.
Alarm OR
Ex.C3
0: None
0: None
Special OFF setup
Ex.C3
----
0: As usual.
Delay time unit
Ex.C3
2.1min
0: 0.1s
Event main setting
Ex
----
0
(low limit)
Event sub-setting
Ex.SB
----
----
(high limit)
Hysteresis
Ex.HY
----
5
ON delay
Ex.ON
30
0
OFF delay
Ex.OF
0
0
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......