![Yamatake SDC35 User Manual Download Page 109](http://html.mh-extra.com/html/yamatake/sdc35/sdc35_user-manual_905228109.webp)
5-51
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
The following Table shows the contents of the dI settings:
(Note 1) Signal edge from
OFF to ON
or from
ON to OFF
is valid during step operation.
(Note 2) Signal edge from
OFF to ON
or from
ON to OFF
is valid.
(Note 3) Signal edge from
OFF to ON
is valid.
■
Event channel definitions
When the operation type is the timer start/stop, a target Event channel can be set.
• When the operation type of the same internal contact No. is set at “Timer
stop/start”, the display and setting can be made.
Item (Bank)
Display
Contents
Initial value
User level
Internal Contact 1 Event
channel definition
(DI Assignment bank)
0: Every internal event
1 to 8: Internal event number
0
High function
0
Internal Contact 2 Event
channel definition
(DI Assignment bank)
0
Internal Contact 3 Event
channel definition
(DI Assignment bank)
Set value
Function
Operation at OFF
Operation at ON
0
No function
None
None
1
LSP group selection (0/+1)
LSP No.: +0
LSP No.: +1
2
LSP group selection (0/+2)
LSP No.: +0
LSP No.: +2
3
LSP group selection (0/+4)
LSP No.: +0
LSP No.: +4
4
PID group selection (0/+1)
PID group No.: +0
PID group No.: +1
5
PID group selection (0/+2)
PID group No.: +0
PID group No.: +2
6
PID group selection (0/+4)
PID group No.: +0
PID group No.: +4
7
RUN/READY mode selection (Note 1)
RUN
READY
8
AUTO/MANUAL mode selection
AUTO
MANUAL
9
LSP/RSP mode selection
LSP
RSP
10
AT (Auto tuning) Stop/Start (Note 2)
AT Stop
AT Start
11
ST (Self-tuning) disabled/enabled
Invalid
Invalid
12
Control action direct/reverse selection
Set action
Reverse action of setting
13
SP ramp enabled/disabled
SP ramp enabled
SP ramp disabled
14
PV value hold
No-hold
Hold
15
PV Max. hold
No-hold
Hold
16
PV Min. hold
No-hold
Hold
17
Timer Stop/Start
Timer stop
Timer start
18
Release all DO latches
Continue if latch exists.
Latch release
19
Advance operation (Note 3)
Step operation continued.
Moves to next SOAK or RAMP.
20
Step hold
Step operation continued.
Hold
0
Internal Contact 4 Event
channel definition
(DI Assignment bank)
0
Internal Contact 5 Event
channel definition
(DI Assignment bank)
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......