PV input range table (Thermocouple)
●
PV input range table (RTD)
*1: If ROM version 1 of the instrument information bank (
Id02
) is prior to 2.04, a setting of “3” for the PV input
range type (C01) will result in display of the K thermocouple 0–800˚C range with no decimal point.
*2: The indicated low limit for a B thermocouple is 20˚C.
However, if ROM version 1 of the instrument information bank(
Id02
) is prior to 2.04, the value is -180˚C.
*3: (Not setting) fixed when Fahrenheit settings.
*4: (No decimal point) fixed when Fahrenheit settings.
●
PV input range table (DC voltage/DC current)
Handling Precautions
• When the C01 PV input range number is set, the decimal point position
and range are initially set automatically as shown in the tables. For
details on the decimal point, refer to
(decimal point position) on page 5-5.
• For details about the accuracy of each PV range type, refer to;
Chapter 13, SPECIFICATIONS (on page 13-1).
5-2
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
C01
Sensor type
Range (C05, C06)
C04
C04
C04 initial value
set value
display range when C01 settings
81
0 to 10mV
• Scaling range is -1999 to +9999.
❍
0 to 3
No change
82
-10 to +10mV
• When C01 is changed, the range (C05, C06)
❍
0 to 3
No change
83
0 to 100mV
default defaults to 0 to 1000.
❍
0 to 3
No change
84
0 to 1V
❍
0 to 3
No change
86
1 to 5V
❍
0 to 3
No change
87
0 to 5V
❍
0 to 3
No change
88
0 to 10V
❍
0 to 3
No change
89
0 to 20mA
❍
0 to 3
No change
90
4 to 20mA
❍
0 to 3
No change
C01
Sensor
Range
Range
C04
C04
C04 initial value
set value
type
(Celsius)
(Fahrenheit)
display range *3
when C01 or C02
settings *4
1
K
-200 to +1200˚C -300 to + 2200˚F
----
(Not setting) (No decimal point)
2
K
0 to 1200˚C
0 to 2200˚F
----
(Not setting) (No decimal point)
3
K
0.0 to 800.0˚C
0 to 1500˚F
❍
0 to 1
0
4
K
0.0 to 600.0˚C
0 to 1100˚F
❍
0 to 1
1
5
K
0.0 to 400.0˚C
0 to 700˚F
❍
0 to 1
1
6
K
-200.0 to +400.0˚C -300 to + 700˚F
❍
0 to 1
1
7
K
-200.0 to +200.0˚C -300 to + 400˚F
❍
0 to 1
1
8
J
0 to 1200˚C
0 to 2200˚F
----
(Not setting) (No decimal point)
9
J
0.0 to 800.0˚C
0 to 1500˚F
❍
0 to 1
1
10
J
0.0 to 600.0˚C
0 to 1100˚F
❍
0 to 1
1
11
J
-200.0 to +400.0˚C -300 to + 700˚F
❍
0 to 1
1
12
E
0.0 to 800.0˚C
0 to 1500˚F
❍
0 to 1
1
13
E
0.0 to 600.0˚C
0 to 1100˚F
❍
0 to 1
1
14
T
-200.0 to +400.0˚C -300 to + 700˚F
❍
0 to 1
1
15
R
0 to 1600˚C
0 to 3000˚F
----
(Not setting) (No decimal point)
16
S
0 to 1600˚C
0 to 3000˚F
----
(Not setting) (No decimal point)
17
B
0 to 1800˚C
0 to 3300˚F
----
(Not setting) (No decimal point)
18
N
0 to 1300˚C
0 to 2300˚F
----
(Not setting) (No decimal point)
19
PL II
0 to 1300˚C
0 to 2300˚F
----
(Not setting) (No decimal point)
20
WRe5-26
0 to 1400˚C
0 to 2400˚F
----
(Not setting) (No decimal point)
21
WRe5-26
0 to 2300˚C
0 to 4200˚F
----
(Not setting) (No decimal point)
22
Ni-NiMo
0 to 1300˚C
0 to 2300˚F
----
(Not setting) (No decimal point)
23
PR40-20
0 to 1900˚C
0 to 3400˚F
----
(Not setting) (No decimal point)
24
DIN U -200.0 to +400.0˚C -300 to + 700˚F
❍
0 to 1
1
25
DIN L
-100.0 to +800.0˚C -150 to + 1500˚F
❍
0 to 1
1
26
Gold iron
0.0K to 360.0K
0.0K to 360.0K
❍
0 to 1
1
chromel
C01
Sensor
Range
Range
C04
C04
C04 initial value
set value
type
(Celsius)
(Fahrenheit)
display range *3
when C01 or C02
settings *4
41
Pt100
-200.0 to +500.0˚C -300 to + 900˚F
❍
0 to 1
1
42
JPt100 -200.0 to +500.0˚C -300 to + 900˚F
❍
0 to 1
1
43
Pt100
-200.0 to +200.0˚C -300 to + 400˚F
❍
0 to 1
1
44
JPt100 -200.0 to +200.0˚C -300 to + 400˚F
❍
0 to 1
1
45
Pt100
-100.0 to +300.0˚C -150 to + 500˚F
❍
0 to 1
1
46
JPt100 -100.0 to +300.0˚C -150 to + 500˚F
❍
0 to 1
1
47
Pt100 -100.0 to +200.0˚C -150 to + 400˚F
❍
0 to 1
1
48
JPt100 -100.0 to +200.0˚C -150 to + 400˚F
❍
0 to 1
1
49
Pt100 -100.0 to +150.0˚C -150 to + 300˚F
❍
0 to 1
1
50
JPt100 -100.0 to +150.0˚C -150 to + 300˚F
❍
0 to 1
1
51
Pt100
-50.0 to +200.0˚C
-50 to + 400˚F
❍
0 to 1
1
52
JPt100
-50.0 to +200.0˚C
-50 to + 400˚F
❍
0 to 1
1
53
Pt100
-50.0 to +100.0˚C
-50 to + 200˚F
❍
0 to 1
1
54
JPt100
-50.0 to +100.0˚C
-50 to + 200˚F
❍
0 to 1
1
55
Pt100
–60.0 to +40.0˚C -60 to + 100˚F
❍
0 to 1
1
56
JPt100 –60.0 to +40.0˚C -60 to + 100˚F
❍
0 to 1
1
57
Pt100
–40.0 to +60.0˚C -40 to + 140˚F
❍
0 to 1
1
58
JPt100 –40.0 to +60.0˚C -40 to + 140˚F
❍
0 to 1
1
59
Pt100 –10.00 to +60.00˚C -10 to + 140˚F
❍
0 to 2
2
60
JPt100 –10.00 to +60.00˚C -10 to + 140˚F
❍
0 to 2
2
61
Pt100
0.0 to 100.0˚C
0 to 200˚F
❍
0 to 1
1
62
JPt100
0.0 to 100.0˚C
0 to 200˚F
❍
0 to 1
1
63
Pt100
0.0 to 200.0˚C
0 to 400˚F
❍
0 to 1
1
64
JPt100
0.0 to 200.0˚C
0 to 400˚F
❍
0 to 1
1
65
Pt100
0.0 to 300.0˚C
0 to 500˚F
❍
0 to 1
1
66
JPt100
0.0 to 300.0˚C
0 to 500˚F
❍
0 to 1
1
67
Pt100
0.0 to 500.0˚C
0 to 900˚F
❍
0 to 1
1
68
JPt100
0.0 to 500.0˚C
0 to 900˚F
❍
0 to 1
1
Summary of Contents for SDC35
Page 16: ......
Page 17: ......
Page 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Page 32: ......
Page 46: ......
Page 58: ......
Page 71: ......
Page 84: ......
Page 95: ......
Page 172: ......
Page 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Page 211: ......
Page 230: ......
Page 240: ......
Page 248: ......
Page 260: ......
Page 268: ......
Page 270: ......
Page 279: ......